Fluke 1760 User Manual page 85

Power quality recorder
Hide thumbs Also See for 1760:
Table of Contents

Advertisement

Electrical Characteristics
Nominal current In:
Measuring ranges:
Crest factor:
Peak current:
Max. non destructive current:
Conductor position influence:
Error due to adjacent conductor:
Phase error (to reference conditions):
Frequency range (clamp without the
instrument):
Temperature coefficient:
Safety:
General Characteristics
Maximum conductor size:
Cable length:
Operating temperature range:
Storage temperature range:
Operating humidity:
Weight (per clamp):
Order-number:
Reference Conditions
Environment temperature range:
Humidity:
Current:
Distortion factor:
Safety Standards
IEC/EN 61010-1 2
IEC/EN 61010-2-032
IEC/EN 61010-031
EMC Standards
EN61326 –1:2006
1 A/10 A AC rms
0.01 A – 1 A or 0.1 A – 10 A
< 3
3.7 A/37 A
Up to 100 A rms
< 0.5 % of range for 50/60 Hz
≤ 15 mA/A for 50 Hz
< ±0.5 degrees
40 Hz – 10 kHz (−3 dB)
0.015 % of range/ °C
300 V CAT IV, type C sensor, pollution
degree 2
Diameter: 15 mm.
Bus bar: 15 x 17 mm
2 m
−10 °C - +55 °C
−20 - +70 °C
15 % - 85 % (non-condensing)
220 g
2540445
+18 °C to +26 °C
20 to 75 % rh
Sinusoidal waveform with 48 to 65 Hz
<1 %, no DC component, stray field <40 A/m,
conductor centered within the clamp jaws
nd
edition
Options and Accessories