Flexi Current Sensor 3000 A/6000 A - Fluke 1760 User Manual

Power quality recorder
Hide thumbs Also See for 1760:
Table of Contents

Advertisement

1760
Users Manual

Flexi Current Sensor 3000 A/6000 A

This current probe has been designed for non intrusive, accurate ac current measurements.
Using the latest technologies (internal memory for calibration data) provides current
measurements between 30 A and 6000 A. The measurement range can be selected in the
PQ Analyze software: IAC3000 or IAC6000.
To protect against electrical shock:
Electrical Characteristics
Nominal current In:
Measuring ranges:
Peak current:
Max. non destructive current:
Intrinsic error:
Linearity (10 % - 100 % of In):
Conductor position influence:
Error due to adjacent conductor:
Phase error (to reference conditions):
6-24
Utilize the clamps only on insulated conductors, max.
600 V rms or dc to ground.
Use personal protective equipment measures as required
by local government agencies, when attaching clamps to
live circuits.
XW Warning
3000 A, 6000 A AC rms
30 A ... 3000 A or 60 A ... 6000 A AC
10 kA, 19 kA
up to 19 kA rms
< ±2 % of mv
±0.2 % of In
< ±2 % of m.v, distance to measuring head
>30 mm
≤ ±2 A (Iext = 500 A, distance to head
>200 mm)
< ± 0.5 degrees
ep1210a-phase-1000a.bmp