Master Reset (P999)
Returns all parameters to default settings.
1.
Press PROGRAM
2.
Press DISPLAY
3.
Key in 999.
4.
Press CLEAR
then
and initiate reset. The LCD displays C.ALL.
5.
Reset complete. (Reset takes several seconds
to complete.
Quick Setup: steps 1 to 9
1. Select language (P010: Language)
Numeric/None
0
*
English
1
German
Value
2
French
3
Spanish
4
2. Set P001: Operation (measurement mode)
Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.
0
Instrument out of service.
Level returns distance to material level referenced from Empty (process empty level). The
1
reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
Value
2
Space returns distance to material level referenced from Span (process full level).
3 * Distance returns distance to material level from reference point.
mA Output with Level, Space, and Distance operation
Level
(P001 = 1)
Span
P006
P007
Empty
Page EN-8
SITRANS LR 200 – QUICK START MANUAL
then DISPLAY
to activate PROGRAM mode.
,
to open parameter fields.
ENTER
, to Clear All
Space
(P001 = 2)
(4 mA)
(20 mA)
Span
0%
100%
Space
Level
Empty
100%
0%
(20 mA)
(4 mA)
Distance
(P001 = 3)
(4 mA)
0%
Span
Distance
Empty
100%
(20 mA)
7ML19985QL81