PROGRAM Mode Display

3
2
1
7
Programming
Set parameters to suit your specific application.
Activate PROGRAM mode at any time, to change parameter values and set
operating conditions.
For local programming, use the Siemens-Milltronics hand programmer.
If you are programming from a distance, you can use either a HART handheld
communicator or a PC running Simatic PDM.

Hand programmer

For direct access to SITRANS LR 200, point the programmer at the SITRANS LR 200 display and
press the keys.
Hand-held programmer
Display
max. 300 mm
(12")
Security: (P000: Lock)
Values
Value stored in P069
other
Factory setting for P069 is 1954: after a new value is entered and accepted, it becomes the
default setting.
Page EN-6
SITRANS LR 200 – QUICK START MANUAL
1– Primary Reading (displays parameter value)
2– Secondary Reading (displays parameter number)
3– Programming indicator
7– Auxiliary Reading (displays parameter names for P001 to
P010, if a language is selected. It displays the index value
for indexed parameters, such as P054).
Key
Decimal point
Negative value
CLEAR value
TOGGLE between Units and % on parameter
value
End PROGRAM session and enable RUN mode
Update echo quality parameters
Parameter scroll-up
Parameter scroll-down
DISPLAY opens parameter fields
ENTER the displayed value
Description
* Lock off: programming permitted
Lock activated: no changes permitted
Programming Mode
7ML19985QL81