LR-200QS-EN.fm Page 4 Wednesday, March 12, 2003 3:51 PM
Avoid central locations on vessels
Coni
Conical
Flat
preferred
locate the antenna away from the side wall, to
avoid interference from indirect echoes
avoid interference from objects such as
ladders or pipes, which can cause false
reflections
s.
• Use the 100 mm (4") shield on nozzles that are 100 mm (4") in length, or shorter.
• Use the 250 mm (10") shield on nozzles that are 250 mm (10") in length, or shorter.
Wiring
Power
WARNINGS:
dc terminals shall be supplied from an SELV source in accordance with
IEC-1010-1 Annex H.
All field wiring must have insulation suitable for rated input voltages.

Connecting SITRANS LR 200

Notes:
For complete wiring instructions, please refer to the Instruction Manual.
Use shielded, twisted pair cable (wire gauge 14-22).
Separate cables and conduits
wiring practices, or electrical codes.
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
Page EN-4
SITRANS LR 200 – QUICK START MANUAL
Fl
at
Parabolic
undesirable
To provide optimum signal conditions on a manhole cover, locate
the antenna off-center relative to the cover, typically 100 mm
(4") from the side of the manhole
minimum
100 mm (4")
1
1
may be required to conform to standard instrumentation
min. 300 mm (1') for every
3 m (10') of vessel height.
beam
angle
o
20
minimum
10 mm (0.4")
7ML19985QL81