Avoid central locations on vessels
Coni
Conical
Flat
preferred
•
locate the antenna away from the side wall, to
avoid interference from indirect echoes
•
avoid interference from objects such as
ladders or pipes, which can cause false
reflections
s.
• Use the 100 mm (4") shield on nozzles that are 100 mm (4") in length, or shorter.
• Use the 250 mm (10") shield on nozzles that are 250 mm (10") in length, or shorter.
Wiring
Power
WARNINGS:
dc terminals shall be supplied from an SELV source in accordance with
IEC-1010-1 Annex H.
All field wiring must have insulation suitable for rated input voltages.
Connecting SITRANS LR 200
Notes:
•
For complete wiring instructions, please refer to the Instruction Manual.
•
Use shielded, twisted pair cable (wire gauge 14-22).
•
Separate cables and conduits
wiring practices, or electrical codes.
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
Page EN-4
SITRANS LR 200 – QUICK START MANUAL
Fl
at
Parabolic
undesirable
To provide optimum signal conditions on a manhole cover, locate
the antenna off-center relative to the cover, typically 100 mm
(4") from the side of the manhole
minimum
100 mm (4")
1
1
may be required to conform to standard instrumentation
min. 300 mm (1') for every
3 m (10') of vessel height.
beam
angle
o
20
minimum
10 mm (0.4")