WIRING and ACCESSORIES
Power Supply
Fuse
PD
R
S
T
(+1)
( L1 )
( L2 )
( L3 )
P
(+)
Inverter
R0
RB
T0
N
(-)
( T1 )
( T2 )
( T3 )
U
V
W
Motor
IM
25
Motor Output
Input
Model
Voltage
(kW(HP))
0.4(1/2)
SJ300-004LFU
0.7(1)
SJ300-007LFU
1.5(2)
SJ300-015LFU
2.2(3)
SJ300-022LFU
3.7(5)
SJ300-037LFU
5.5(7.5)
SJ300-055LFU
7.5(10)
SJ300-075LFU
200V
11(15)
SJ300-110LFU
15(20)
SJ300-150LFU
18.5(25)
SJ300-185LFU
22(30)
SJ300-220LFU
30(40)
SJ300-300LFU
37(50)
SJ300-370LFU
45(60)
SJ300-450LFU
55(75)
SJ300-550LFU
0.7(1)
SJ300-007HFU/E
1.5(2)
SJ300-015HFU/E
2.2(3)
SJ300-022HFU/E
3.7(5)
SJ300-040HFU/E
5.5(7.5)
SJ300-055HFU/E
7.5(10)
SJ300-075HFU/E
11(15)
SJ300-110HFU/E
15(20)
SJ300-150HFU/E
18.5(25)
SJ300-185HFU/E
22(30)
SJ300-220HFU/E
400V
30(40)
SJ300-300HFU/E
37(50)
SJ300-370HFU/E
45(60)
SJ300-450HFU/E
55(75)
SJ300-550HFU/E
75(100)
SJ300-750HFU/E
90(125)
SJ300-900HFU/E
110(150)
SJ300-1100HFU/E
132 (175)
SJ300-1320HFE
150 (200)
SJ300-1500HFU
Note 1: Field wiring connection must be made by a UL and c-UL listed closed-loop terminal connector sized for
the wire gauge involved.
Connector must be fixed using the crimping tool specified by the connector manufacturer.
Note 2: Be sure to use large wire gauges for power wiring if the distance exceeds 20m (66ft).
Name
Input side AC reactor
EMI filter
Radio noise filter
Radio noise filter (Capacitor filter)
DC link choke
Braking resistor
Braking unit
Output side noise filter
Radio noise filter
AC reactor
LCR filter
Note: An EMI filter is required for European EMC directive and C-Tick, but the others are not for this purpose.

Wiring

Power Lines
AWG
2
mm
20
0.5
18
0.8
14
2.1
14
2.1
10
5.3
8
8.4
6
13.3
4
21.2
2
33.6
4
×
2
21.2
×
2
4
×2
21.2
2
×
2
×
2
33.6
×
2
2
×
2
33.6
×
2
1
1 (75℃)
42.4
2
×
×
2/0
2
×
53.5
×
2
20
0.5
18
0.8
16
1.3
14
2.1
12
3.3
10
5.3
8
8.4
6
13.3
6
13.3
4
21.2
3
26.7
4
×2
21.2
×
2
1
×
1 (75℃)
42.4
2
2
×
33.6
×
2
1
×
1 (75℃)
42.4
×
2
1
×
1 (75℃)
42.4
2
×
1/0
×2
53.5
×
2
3/0
×
2
85.0
×
2
3/0
×
2
85.0
2
×
Function
This is useful in suppressing harmonics induced on the power sup-
ply lines, or when the main power voltage imbalance exceeds 3%
(and power source capacity is more than 500kVA), or to smooth out
line fluctuations. It also improves the power factor.
Reduces the conducted noise on the power supply wiring generat-
ed by the inverter. Connect to the inverter input side.
Electrical noise interference may occur on nearby equipment such
as a radio receiver. This magnetic choke filter helps reduce radiat-
ed noise (can also be used on output).
This capacitor filter reduces radiated noise from the main power
wires in the inverter input side.
Suppresses harmonics generated by the inverter.
This is useful for increasing the inverter's control torque for high
duty-cycle (on-off) applications, and improving the decelerating
capability.
Reduces radiated noise from wiring in the inverter output side.
Electrical noise interference may occur on nearby equipment such
as a radio receiver. This magnetic choke filter helps reduce radiat-
ed noise (can also be used on input).
This reactor reduces the vibration in the motor caused by the inver-
ter's switching waveforms, by smoothing the waveforms to approxi-
mate commercial power quality. It is also useful when wiring from
the inverter to the motor is more than 10m in length, to reduce har-
monics.
Sine wave shaping filter for the output side.
Fuse
(Class J)
Signal Lines
10
10
10
15
20
30
0.75mm
2
40
shielded
60
wire
80
100
125
150
175
225
250
10
10
10
15
15
20
30
40
50
2
0.75mm
60
shielded
wire
70
90
125
125
175
200
250
300
300

Hide quick links: