●B GROUP: FINE TUNING FUNCTIONS
Code
Name
b001
Selection of automatic restart mode
b002
Allowable instantaneous power failure time
b003
Time delay enforced before motor restart
b004
Instantaneous power failure and under-voltage trip enable
Number of restarts after instantaneous power
b005
failure and under-voltage trip events
b006
Phase loss detection enable
b007
Restart frequency threshold
b012
Level of electronic thermal setting
Level of electronic thermal setting for second motor
b212
Level of electronic thermal setting for third motor
b312
b013
Electronic thermal characteristics
b213
Electronic thermal characteristics for second motor
b313
Electronic thermal characteristics for third motor
b015
Free-setting electronic thermal frequency (1)
b016
Free-setting electronic thermal current (1)
b017
Free-setting electronic thermal frequency (2)
b018
Free-setting electronic thermal current (2)
b019
Free-setting electronic thermal frequency (3)
b020
Free-setting electronic thermal current (3)
b021
Overload restriction operation mode
b022
Overload restriction setting
b023
Deceleration rate at overload restriction
b024
Overload restriction operation mode (2)
Overload restriction setting (2)
b025
b026
Deceleration rate at overload restriction (2)
b031
Software lock mode selection
b034
RUN/ power-on warning time
b035
Rotational direction restriction
b036
Reduced voltage soft start selection
b037
Function code display restriction
b040
Torque limit selection
b041
Torque limit(1) (Forward-driving in 4-quadrant mode)
Torque limit(2) (Reverse-regenerating in 4-quadrant mode)
b042
Torque limit(3) (Reverse-driving in 4-quadrant mode)
b043
b044
Torque limit(4) (Forward-regenerating in 4-quadrant mode)
b045
Torque limit LADSTOP enable
b046
Reverse RUN protection enable
Controlled deceleration and stop on power loss
b050
b051
DC bus voltage trigger level during power loss
Over-voltage threshold during power loss
b052
b053
Deceleration time setting during power loss
Initial output frequency decrease during
b054
power loss
b080
AM terminal analog meter adjustment
b081
FM terminal analog meter adjustment
b082
Start frequency adjustment
b083
Carrier frequency setting
Initialization mode
b084
b085
Country code for initialization
b086
Frequency scaling conversion factor
b087
STOP key enable
b088
Resume on free-run stop cancellation mode
b090
Dynamic braking usage ratio
b091
Stop mode selection
b092
Cooling fan control
b095
Dynamic braking control
b096
Dynamic braking activation level
b098
Thermistor for thermal protection control
b099
Thermistor for thermal protection level setting
Note:[ ]75kW and over
15
Description
00(Alarm output after trip, automatic restart disable) / 01(Restart at 0Hz) / 02(Re-
sume operation after frequency matching)/ 03(Resume previous frequency after
frequency matching, then decelerate to stop and display trip information)
0.3 - 25.0sec.
0.3 - 100.0sec.
00(Disable) / 01(Enable) / 02(Disable during stop and deceleration to stop)
00(16 times) / 01(Always restart)
00(Disable) / 01(Enable)
0.00 - 99.99/100.0 - 400.0Hz
0.20
rated current-1.20
rated current
×
×
0.20
×
rated current-1.20
×
rated current
0.20
rated current-1.20
rated current
×
×
00(Reduced torque) / 01(Constant torque) / 02(V/f free-setting)
00(Reduced torque) / 01(Constant torque) / 02(V/f free-setting)
00(Reduced torque) / 01(Constant torque) / 02(V/f free-setting)
0.-400.Hz
0.0-1000.A
0.-400.Hz
0.0-1000.A
0.-400.Hz
0.0-1000.A
00(Disable)/ 01(Enable during accel./constant speed)
/ 02(Enable during constant speed)
/ 03(Enable during accel./constant speed(Speed increase when regenerating))
rated current [ - 1.80
0.50
rated current-2.00
×
×
0.10-30.00
00(Disable) / 01(Enable during accel./constant speed)
/ 02(Enable during constant speed)
/ 03(Enable during accel./constant speed(Speed increase when regenerating))
rated current [ - 1.80
0.50
rated current-2.00
×
×
0.10-30.00
00(All parameters except b031 are locked when SFT from terminal is on)/ 01(All
parameters except b031 and output frequency F001 are locked when SFT from
terminal is on)/ 02(All parameters except b031 are locked)/ 03(All parameters
except b031 and output frequency F001 are locked)/ 10(Run-time data edit
mode)
0.-6553(65,530hr) (Output to intelligent terminal)
00(Enabled for both directions)/ 01(Enabled for forward)/ 02(Enabled for reverse)
00(Short)-06(Long)
00(All)/ 01(Utilized functions)/ 02(User-selected functions only)
00(4-quadrant setting)/ 01(Terminal input)/ 02(Analog O2 input)
/ 03(Expansion card 1)/ 04(Expansion card 2)
0.-200. % / no (Torque limit disable)
0.-200. % / no (Torque limit disable)
0.-200. % / no (Torque limit disable)
0.-200. % / no (Torque limit disable)
00(Disable)/ 01(Enable)
00(Disable)/ 01(Enable)
00(Disable)/ 01(Enable)
0.0 - 1000.V
0.0 - 1000.V
0.01 - 99.99/100.0 - 999.9/1000. - 3600.sec.
0.00 - 10.00Hz
0-255
0-255
0.10-9.99Hz
0.5-15.0kHz (To be derated) [0.5-10kHz]
00(Trip history clear) / 01(Parameter initialization)
/ 02(Trip history clear and parameter initialization)
00(Japanese version)/ 01(European version)/ 02(North American version)
0.1-99.9
00(Enable) / 01(Disable)
00(Restart at 0Hz) / 01(Resume operation after frequency matching)
0.0-100.0%
00(Deceleration to stop) / 01(Free-run stop)
00(Fan is always ON) / 01(Fan is ON during RUN including 5 min. after power-on and stop)
00(Disable) / 01(Enable during run) / 02(Enable during stop)
330-380/ 660-760V
00(Disable) / 01(PTC enable) / 02(NTC enable)
0.0-9999.Ω
Default Setting
-FE(CE) -FU(UL)
00
00
1.0
1.0
1.0
1.0
00
00
00
00
00
00
0.00
0.00
Rated current
Rated current
Rated current
Rated current
Rated current
Rated current
01
01
01
01
01
01
0.
0.
0.0
0.0
0.
0.
0.0
0.0
0.
0.
0.0
0.0
01
01
Rated
Rated
rated current]
×
current
×
1.50
current
1.50
×
1.00
1.00
01
01
Rated
Rated
rated current]
×
current
1.50
current
1.50
×
×
1.00
1.00
01
01
0.
0.
00
00
06
06
00
00
00
00
150.
150.
150.
150.
150.
150.
150.
150.
00
00
00
00
00
00
0.0
0.0
0.0
0.0
1.00
1.00
0.00
0.00
180
180
60
60
0.50
0.50
5.0[3.0]
5.0[3.0]
00
00
01
02
1.0
1.0
00
00
00
00
0.0
0.0
00
00
00
00
00
00
360/720
360/720
00
00
3000.
3000.
[
= Allowed
]
= Not permitted
×
Run-time
Run-time Data Edit
Setting
(Enabled at b031)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
  
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×