Siemens LMV52 series User Manual page 16

Burner management system for forced draft burners. cox supervision and control
Hide thumbs Also See for LMV52 series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
B7
38
O2M
B7
3E
O2M
B7
3F
O2M
B7
41
LMV5
B7
42
LMV5
BE
01
LMV5
16/17
Building Technologies Division
User Manual LMV5...
List of error messages of LMV5 system
Display
No valid COx signal from PLL52
No valid COx signal from PLL52
No valid COx signal from PLL52
Cable connection to the PLL52
No valid COx signal from PLL52
disconnected
PLL52 is sending messages but these are
No valid COx signal from PLL52
incorrect
COx supervision must not be combined
COx operating mode is not
with the setting for a temperature-
possible with the selected O2
compensated start mode in O2 trim
operating mode
control. Both settings use the supply air
sensor
Meaning for the LMV5 system
Fault during copying of a parameter page
External plausibility fault.
This type of fault covers possible faults
occurring due to invalid presettings in the
drive commands. In response, the
presettings will be ignored
Internal plausibility fault.
This type of fault covers possible errors
that cannot practically occur
Troubleshooting
Reset the unit
Attention!
If fault occurred during parameterization:
Check the parameters changed last.
If fault cannot be rectified by the reset:
Restore parameters from AZL5.
Otherwise, replace the O2 module
Reset the unit
Attention!
If fault occurred during parameterization:
Check the parameters changed last.
If fault cannot be rectified by the reset:
Restore parameters from AZL5.
Otherwise, replace the O2 module
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
Check CAN wiring / check power supply PLL52...
Check cable connection / wiring to the PLL52
Parameterize the O2 start mode to standard or to
IgnPtWoutTC, or set COx supervision to deactivated.
CC1A7550.5en
07.07.2015

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv52.4 series