Section 7
Logical node data model
7.5
7.5.1
7.5.1.1
Table 11:
T2WPDIF Logical node data
DO name
DO type
Str
aACD
Mod
aINC
Beh
aINS
Op
bACT
OpnCTVal
v1INS
Table continues on next page
86

Logical nodes for protection functions

Differential protection PDIF

Transformer differential protection, two winding T2WPDIF

LN type
LN prefix LN class Function block name
T2WPDIF (revision 1) T2W
DA name
FC
general
ST
phsA
ST
phsB
ST
phsC
ST
q
ST
t
ST
Oper.ctlVal
CO
Oper.origin.orCat
CO
Oper.origin.orIdent
CO
Oper.ctlNum
CO
Oper.T
CO
Oper.Test
CO
Oper.Check
CO
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
general
ST
q
ST
t
ST
stVal
ST
PDIF
T2WPDIF
T
Signal
-
START
-
STL1
-
STL2
-
STL3
-
START
-
START
-
Mod
-
Mod
-
Mod
-
Mod
-
Mod
-
Mod
-
Mod
-
-
-
-
-
-
-
Beh
-
Beh
-
Beh
T
TRIP
T
TRIP
T
TRIP
-
OCTSIDE
1MRK 511 349-UEN -
Mon/C
Description
md
Mon
Common start signal from any
phase
Mon
Start signal from phase L1
Mon
Start signal from phase L2
Mon
Start signal from phase L3
Mon
Quality: Common start signal from
any phase
Mon
Timestamp: Common start signal
from any phase
Cmd
Mode parameter
Cmd
Mode parameter
Cmd
Mode parameter
Cmd
Mode parameter
Cmd
Mode parameter
Cmd
Mode parameter
Cmd
Mode parameter
Mon
Mode status parameter for 61850
Mon
Quality: Mode status parameter for
61850
Mon
Timestamp: Mode status
parameter for 61850
Mon
Behaviour parameter
Mon
Quality: Behaviour parameter
Mon
Timestamp: Behaviour parameter
Mon
General, common trip signal
Mon
Quality: General, common trip
signal
Mon
Timestamp: General, common trip
signal
Mon
Open CT side : 1 -> W 1 (pri), 2 ->
W 2 (sec)
670 series 2.1 IEC