Zone Programming

NOTE: If a device is assigned to a zone which is already programmed, a wireless zone will overwrite a hardwire zone.

Zone Definition Values

To program zone definitions and assign options:
1.
Press and hold 0.
2.
Enter your installer code or maintenance code.
3.
Enter the four-digit zone you wish to program.
4.
Enter the two-digit zone definition, refer to table 4.
5.
Assign the partition, refer to table 5. By default, all zones are assigned to partition 1.
6.
Select or de-select zone options using buttons 1 through 8, see table 6 or table 7.
7.
Press the # key to save and proceed to the next zone. Repeat steps 3 to 6 for all remaining zones.
Table 4: Zone definitions
Input
Description
Value
00
Disabled (default)
01
Entry delay 1*
02
Entry delay 2*
03
Entry delay 1 (full arm)
04
Entry delay 2 (full arm)
05
Follow*
06
Follow (sleep/full arm)
07
Follow (full arm)
08
Instant*
09
Instant (sleep/full arm)
10
Instant (full arm)
11
Instant fire*
12
Delayed fire*
13
Instant fire silent*
14
Delayed fire silent*
15
24 hr. buzzer*
16
24 hr. burglary*
17
24 hr. hold-up*
18
24 hr. gas*
19
24 hr. heat*
20
24 hr. water*
21
24 hr. freeze*
22
24 hr. panic*
23
Follow no pre-alarm*
24
Instant no pre-alarm*
25
Keyswitch maintain*
26
Keyswitch momentary*
27
Delay 1 (sleep/full arm)
28
Delay 2 (sleep/full arm)
29
Unarmed*
30-32
Future use
33
Custom template 1†
34
Custom template 2†
35
Custom template 3
36
Custom template 4
*: Zone definitions that can be used in custom zone templates.
-: Zone definitions remain the same, regardless of arming type.
†: WARNING: Do not use these definitions for a common zone. The definition of a common zone follows the definition relative to the
area that gets the lowest level of arming. A problem may occur if a common zone follows an area armed in Stay/Sleep and an area
armed in Full. The resulting zone definition will be the one relative to the lowest level of arming which is Stay armed. The zone will
be considered as armed in both areas.
6 | Zone Programming
Arming Type
OFF
Stay Arm
-
-
Not armed
Entry delay 1
Not armed
Entry delay 2
Not armed
Not armed
Not armed
Not armed
Not armed
Follow
Not armed
Not armed
Not armed
Not armed
Not armed
Instant
Not armed
Not armed
Not armed
Not armed
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Not armed
-
Not armed
-
-
-
-
-
Not armed
Not armed
Not armed
Not armed
Not armed
Not armed
-
-
Not armed
Instant
Not armed
Not armed
Not armed
Entry delay 1
Not armed
Instant
Sleep Arm
Full Arm
-
-
Entry delay 1
Entry delay 1
Entry delay 2
Entry delay 2
Not armed
Entry delay 1
Not armed
Entry delay 2
Follow
Follow
Follow
Follow
Not armed
Follow
Instant
Instant
Instant
Instant
Not armed
Instant
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Entry delay 1
Entry delay 1
Entry delay 2
Entry delay 2
Not armed
Not armed
-
-
Instant
Not armed
Instant
Not armed
Instant
Entry delay 1
Instant
Entry delay 1
MG6250 • Section Programming Guide
Table 5: Partition assignment
Partition assignment
Input
Description
Value
1
Assign to partition 1
2
Assign to partition 2
3
Assign to both partitions
Table 6: Zone options
Zone options
Input
Description
Value
1
Auto zone shutdown
2
Bypassable zone
3
RF zone supervision
6
Intellizone delay
7
Delay arm transmission
8
Force arming
Input Value
Zone Alarm Type
4
5
OFF
OFF
Audible alarm
ON
OFF
Silent alarm
OFF
ON
Audible pulse
ON
ON
Report only
Table 7: Keyswitch options
Keyswitch options
Input Value
Levels of Arming
1
2
OFF
OFF
Disarm
ON
OFF
Stay Arm
OFF
ON
Sleep Arm
ON
ON
Full Arm
Input Value
Description
3
-
4
Disarm partial arm only
5
Arm only
6
-
Version 1.6