5.

CAPACITY COMPENSATION RATE FOR PIPE LENGTH

AND HEIGHT DIFFERENCE
MODEL
: AOU9RLFC, AOU12RLFC
COOLING
Indoor unit is
higher than
outdoor unit.
Height
difference H
Indoor unit is
lower than
outdoor unit
HEATING
Indoor unit is
higher than
outdoor unit.
Height
difference H
Indoor unit is
lower than
outdoor unit
Indoor unit
Connection pipe
 1 Indoor unit is higher than outdoor unit.
15m
50ft.
Û 1
10m
33ft.
7.5m
25ft.
5m
17ft.
0m
0ft.
-5m
-17ft.
Û 2
-7.5m
-25ft.
-10m
-33ft.
-15m
-50ft.
15m
50ft.
Û 1
10m
33ft.
7.5m
25ft.
5m
17ft.
0m
0ft.
-5m
-17ft.
Û 2
-7.5m
-25ft.
-10m
-33ft.
-15m
-50ft.
Height difference H
H
Outdoor unit
5m
7.5m
17ft.
25ft.
-
-
-
-
-
0.988
1.017
0.992
1.025
1.000
1.025
1.000
-
1.000
-
-
-
-
5m
7.5m
17ft.
25ft.
-
-
-
-
-
1.000
1.017
1.000
1.017
1.000
1.012
0.995
-
0.993
-
-
-
-
Outdoor unit
Connection pipe
 2 Indoor unit is lower than outdoor unit.
- (02 - 06) -
Pipe length
10m
15m
33ft.
50ft.
-
0.877
0.956
0.891
0.960
0.895
0.964
0.899
0.971
0.906
0.971
0.906
0.971
0.906
0.971
0.906
-
0.906
Pipe length
10m
15m
33ft.
50ft.
-
0.933
0.981
0.933
0.981
0.933
0.981
0.933
0.981
0.933
0.976
0.928
0.974
0.926
0.971
0.923
-
0.914
H
Indoor unit
20m
67ft.
0.874
0.888
0.892
0.895
0.902
0.902
0.902
0.902
0.902
20m
67ft.
0.925
0.925
0.925
0.925
0.925
0.920
0.918
0.916
0.906

Hide quick links: