INSTALLATION AND SERVICING MANUAL
Note: User Instructions
are contained into Remote Control suppled with the boiler

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KON 1 C24 and is the answer not in the manual?

Questions and answers

Summary of Contents for Unical KON 1 C24

  • Page 1 C24 - C28 - C35 INSTALLATION AND SERVICING MANUAL Note: User Instructions are contained into Remote Control suppled with the boiler...
  • Page 2 http://www.unicalag.it/prodotti/domestico-50/condensazione-gas/2072/kon1 Provisions for proper disposal of the product in accordance with Directive 2002/96/EC At the end of its life cycle the product must not be disposed of as urban waste. It can be taken to a special recycling centre managed by the local authorities, or to a dealer who offers this service. Separate disposal of a domestic appliance avoids possible negative consequences for the environment and human health deriving from inappropriate waste handling and allows the recovery of the materials of which it is made, in order to obtain significant energy and resource savings.
  • Page 3: Table Of Contents

    Attention: this manual contains instructions for the exclusive use of the professionally qualified installer and/or maintenance technician in compliance with current legislation. The user is NOT qualified to intervene on the boiler. The manufacturer will not be held liable in case of damage to persons, animals or objects resulting from failure to comply with the instructions contained in the manuals supplied with the boiler.
  • Page 4: General Information

    Any repairs must be performed solely by personnel regarding installation, use and maintenance safety. authorised by Unical AG S.p.A., using original spare parts only. Failure to comply with the above can com- Keep the booklet with care for further consultation.
  • Page 5: Symbols Used In The Manual

    Any other use is considered improper. Unical AG S.p.A. will not be held liable for any damage resulting from improper use. Use according to the intended purposes also includes strict compliance with the in- structions in this manual.
  • Page 6: Safety Warnings

    1.5 - SAFETY wARNINGS ATTENTION! The boiler cannot be used by children. The boiler can be used by adults and only after having carefully read the user’s ma- nual. Children should be supervised to ensure that they do not play or tamper with the device.
  • Page 7: Technical Data Plate

    1.6 - TECHNICAL DATA PLATE The CE marking KEY: 1 = CE monitoring body certifies the compliance of the equipment with the 2 = Type of boiler essential safety requirements defined in the directi- 3 = Boiler model ves and applicable European regulations and that 4 = Number of stars (directive 92/42 EEC) its functioning satisfy applicable technical stan- 5 = (S.N°) Serial Number...
  • Page 8: Boiler Antifreeze Protection

    The treatment of the supply water ATTENTION! allows to prevent inconveniences ANY DAMAGE TO THE BOILER and maintain the functionality and CAUSED BY THE FORMATION OF efficiency of the generator over time. FOULING OR BY CORROSIVE wA- TER wILL NOT BE COVERED BY The ideal water pH in heating systems THE wARRANTY.
  • Page 9: Technical Features And Dimensions

    TECHNICAL FEATURES AND DIMENSIONS NOTE! For more information 2.1 - TECHNICAL FEATURES See Technical Info from site indicated at pag. 2 2.2 - VIEw wITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS KON 1 C24...
  • Page 10 KON 1 C24 View from above View from below...
  • Page 11 KON 1 C28 - KON 1 C35...
  • Page 12 KON 1 C28 - KON 1 C35 View from above View from below...
  • Page 13 N° C.E. S.E. Description Condensation drain trap Domestic hot water temperature Service panel sensor Manometer FLS Flow switch with cold water filter Gas valve Domestic hot water outlet G ½ Ignition/detection electrode Gas inlet G ¾ /RIL Cold water inlet G ½...
  • Page 14 2.3 - DIAGRAM OF FLOw RATE/PRESSURE AVAILABLE FOR INSTALLATION MODULATING PUMP DIAGRAM OF FLOw RATE/PRESSURE AVAILABLE FOR INSTALLATION KON 1 C24 - C28 - C35 Flow rate (l/h)
  • Page 15 2.4 - OPERATING DATA ACCORDING TO UNI 10348 For the adjustment data: NOZZLES - PRESSURES - DIAPHRAGMS - FLOW RATES - CONSUMPTIONS refer to the paragraph ADAPTATION TO OTHER TYPES OF GAS. KON 1 C24 KON 1 C28 KON 1 C35 Nominal heat input in CH / DHW mode 23,4 / 23,4 28,0 / 28,0 33,0 / 33,0 Minimum heat input with Nat. Gas / Propane...
  • Page 16: General Features

    2.5 - GENERAL FEATURES KON 1 C24 KON 1 C28 KON 1 C35 Appliance category 2H3P 2H3P 2H3P Minimum heat. circuit output (∆t 20 °C) l/min Minimum heating circuit pressure Maximum heating circuit pressure Primary circuit content Maximum operating temperature in heat.
  • Page 17: Installation Instructions

    INSTALLATION INSTRUCTIONS 3.1 - GENERAL wARNINGS ATTENTION! If there is dust and/or if there are aggressive/corrosive vapours ATTENTION! This boiler is intended solely for present in the installation room, the use for which it was expressly the appliance must be protected designed.
  • Page 18: Packaging

    - Warranty children as they are potential sources of danger. - 2 Spare parts form Unical AG S.p.A. will not be held liable for damage to - Certificate of conformity persons, animals or objects due to failure to comply B - Plexy front cover...
  • Page 19: Positioning The Boiler

    3.5 - POSITIONING THE BOILER When choosing the place of the installation of the Since the temperature of the wall on which the boil- appliance, follow the safety instructions below: er is installed and the temperature of the coaxial - Place the appliance in rooms protected from frost. exhaust pipe do not exceed, in normal operating - Avoid installation in rooms with a corrosive or very conditions, a room temperature beyond 60 K, it is...
  • Page 20: Flue Gas Exhaust Pipe Connection

    3.6 - FLUE GAS EXHAUST PIPE CONNECTION FOR BOILERS wITH FORCED DRAUGHT place the flue gas pipe as well. To connect the flue gas exhaust pipe, local and na- tional standards must be observed The boiler is type approved for the exhaust configu- In the event the boiler is replaced, ALwAYS re- rations listed below: C13x...
  • Page 21 Please note: the condensate drain from the These values relate to exhausts/ evacuation system of combustion made by means of rigid pipes and products. smooth original UNICAL.
  • Page 22 (Leave 2 above). It is recommended to only use original Unical exhaust pipes. The supplier will have no contractual or extra-contractual liability for damage caused due to incorrect installation and use and in any case failure to comply with the instructions provided by the manufacturer.
  • Page 23: Connections

    3.7 - CONNECTION Condensation drain 3/4’’ The boiler, during the combustion process, pro- duces condensation that, through pipe “A”, flows Danger! into the trap. The gas connection must be carried out only by a qualified installer who must re- The condensation that forms inside the boiler flows spect and apply that foreseen by relevant into a suitable drain via pipe “B”.
  • Page 24: Filling The System

    3.8 - FILLING THE SYSTEM Unical will not be held liable for dam- Attention! age to persons, animals or objects Do not mix the heating water with in- due to failure to comply with the above correct concentrations of antifreeze instruction.
  • Page 25: Electrical Connections

    3.9 - ELECTRICAL CONNECTIONS Danger! any type of operation on electrical parts, always Only a qualified technician may per- disconnect electrical power and make sure that form the electrical installation. it cannot be reconnected accidentally. Before performing connections or Connection to remote control Connect Bridge to TA1 / OT terminals after removing jumper from TA2.
  • Page 26 The power cable must be replaced by technical personnel authorised by UNICAL AG S.p.A., using original spare parts only. Failure to comply with the above can jeopardise the safety of the appliance. CAVO/CABLE...
  • Page 27: Commissioning

    3.10 - COMMISSIONING Commissioning must be done by profes- failure to comply with the above instruction. sionally qualified personnel. Unical AG Before commissioning the boiler, check that: S.p.A. will not be held liable for damage to persons, animals or objects due to...
  • Page 28: Service Panel

    3.11 - SERVICE PANEL It is located inside the boiler and allows Note: Simbol D - B - C is only rapresen- to make some operations for the exclu- ted in design, is not printed in the panel. sive use of the Authorized Service Centers.
  • Page 29 3.12 - MISURA IN OPERA DEL RENDIMENTO DI COMBUSTIONE 3.12.1 - ACTIVATION OF THE CALIBRATION FUNCTION ATTENTION! The user is NOT authorised to activate the func- Function reserved for Authorised tion described below. Assistance Centres only. ACTIVATION (from Service Panel) By pressing the button (D) for 3 seconds, the calibration function is activated.
  • Page 30 3.12.2 - POSITIONING THE PROBES - measurement of the flue gas temperature and To determine the combustion efficiency content of CO taken in the relevant hole 2. one must make the following measurements: Take the measurements with the generator in - measurement of the combustion air temperature steady state conditions (see par.
  • Page 31: Adjusting The Burner

    3.13 - ADJUSTING THE BURNER Attention, during these operations do not take The following instructions are intended any samples in domestic hot water mode. exclusively for authorised service per- sonnel. All boilers leave the factory already cali- brated and tested, however in the event the gas valve recalibration is required: - Remove the cap and insert the CO2 analysis probe in the flue gas sample point of the intake/...
  • Page 32 For proper operation, the CO values must be calibrated with particular at- tention, observing the values indicated in the table. PRESSURE - FLOw RATES TABLE KON 1 C24 Collector Start-up Type of Effective Heating Supply levels Con- Con- diaphragm power...
  • Page 33: Adaptation Of The Power To The Heating System

    E.g.: KON 1 C24 to decrease the output of the boiler to 17,5 kW, edit parameter HP (about 68) E.g.: KON 1 C28...
  • Page 34: Inspection And Maintenance Instructions

    To assure long-term functioning of your appliance and to avoid altering its approved status, only original Once all maintenance operations are complete Unical AG S.p.A. spare parts must be used. resume boiler operation • Open the heating flow and return pipes, as well If a component needs to be replaced: as the cold water inlet valve (if closed previously).
  • Page 35 It is recommended to use the using a meter and compare the val- products purposely created by ue with that contained in table 3.12. Unical (see system protection The data measured indicates if the ACCESSORIES sect. in the exchanger needs cleaning.
  • Page 36: Remote Control

    4.2 - REMOTE CONTROL EASY r User instructiona are contained into the necessary for adjustment / maintenance of EASY r package the boiler: In this section are indicated only info - Adjust parameter (Par. 4.3) OFF / Sumemr / Winter / Reset faults programs button User information / setting button Automatic / Manual heating program button...
  • Page 37 4.3 - PROGRAMMING OPERATION PARAMETERS Follow info on EASYr to change TSP ATTENTION! parameters. Function reserved for Authorised Assistance Centres only. Press Reset button for 10 sec, display shows menù Press again Reset button to select manù TS = Trasparent parameters o OE = Reserved, TS / OE Parameters not editable.
  • Page 38: Tsp Parameters

    To modify parameters is necessary password TSp Parameter TSp Parameter EASY r EASY r Desciption Min. Max. Desciption Min. Max. Enabled Services: IgL - GPL: Modulation level at 0: CH & DHW disabled start 1: CH enabled FL - NAT: Min Fan Speed 2: DHW enabled 3: CH & DHW enabled FLL - GPL: Min Fan Speed Pump: Post-circulation 0: overrun 5 min. FH - NAT: Max Fan Speed 1: continuous Outdoor minimum FHL - GPL: Max Fan Speed temp °C...
  • Page 39 4.4 - ADAPTATION TO THE USE OF OTHER GAS The boilers are produced for the type of gas specif- ically requested upon ordering. DANGER! The conversion for the operation of the boiler with a type of gas other than that specifically required in the order, must be performed by professionally qualified personnel, in compliance with the standards and regulations...
  • Page 40: Wiring Diagram

    Practical connection board 4.5 - wIRING DIAGRAM Return heating sensor A1..A9 Services connectors Domestic hot water probe (Pred. for R models) Modulating pump control Limit thermostat E. ACC./RIL Water deficiency safety pressure switch Flue gas collector limit thermostat Ignition/detection electrode Gas valve Domestic hot water request flow switch Modulating fan Pump External probe connection terminals Pressure Sensor System TA1 / OT Modulating TA connection terminals Flow heating sensor On/off TA connection terminals...
  • Page 41: Error Code

    4.6 - ERROR CODES The symbol flashes on the display monitor when the boiler detects an anomaly. service 1) In the event of an anomaly that does not stop boiler operation, press the unblock key to display the error code; in the event the boiler is in stand-by, the error code appears and remains fixed on the display.
  • Page 42 SyMBOL CODE CODE DESCRIPTION SOLUTIONS REGOLA- EASY r ON SERVICE FACILE PANEL INCORRECT SENSOR Check the wiring (11) (22) POSITIONING Flow and return sensors in- verted SPEED OUT OF Check fan operation (18) and CONTROL the connections. Alteration of the fan speed; the speed is not reached.
  • Page 43 Replace the board. Flame control damaged INCONVENIENCES SOLUTIONS KON 1 C24 - C28 - C35 Flame noisy Act on parameter ‘’IG’’ using the REGOLAFACILE section ‘’TECHNICAL in cold ignition MENU’’ TSP parameters increasing the value by 5 ÷ 10 % max...
  • Page 44 - export@unical-ag.com - www.unical.eu Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press. Also reserves the right to bring those changes that it will hold necessary to it own products or profits, without jeopardizing its essential characteristics.