Meaning of the LED displays
The tables below explain the meaning of the status and error displays.
LED RUN/ERROR
Table 5- 1
RUN/ERROR status and error displays
LED
RUN
ERROR
Off
Off
Flashes
Off
On
Off
Flashes
Flashes
LED CHx
Table 5- 2
CHx status display
LED CHx
Off
On
Digital input module DI 32x24VDC BA (6ES7521-1BL10-0AA0)
Manual, 12/2016, A5E32363711-AD
Meaning
Voltage missing or too low at backplane bus.
Module is starting up.
Module is ready.
Hardware defective.
Meaning
0 = Status of the input signal.
1 = Status of the input signal.
5.1 Status and error displays
Remedy
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Replace the module.
Remedy
---
---
Diagnostics alarms
19