S ection 5 ·
Instal lation
5

Installation

5.1

Determining the installation location

Install the Powador-proLOG near a telephone or Ethernet con-
nection and a 230 V grid connection. To prevent damage to
the Powador-proLOG or the building's electrical system, keep
the following points in mind when you choose an installation
location:
The Powador-proLOG may not be installed outdoors or
in damp areas. The unit must be protected from moisture
and direct sunlight.
The ambient temperature must be between 0 °C and +55 °C.
There may not be any building installations
(e.g. power, gas or water lines) around the drill holes.
The Powador-proLOG should be placed on a level surface
to prevent damage to the housing.
5.2

Installing the unit

5.2.1 Powador-proLOG S

The unit is suitable for mounting on a top hat rail (size 35 mm).
To make it easy to attach the housing, use a clamping device
to snap it onto (or release it from) the hat rail.
POWADOR proLOG
S
MADE IN GERMANY
+
-
160,00 mm

5.2.2 Powador-proLOG M/L/XL

The unit is suitable for wall mounting. Use the sketch below to
mark the drill holes.
The distance between the screws on the mounting bracket
and the wall should be approx. 3 mm.
Hang the Powador-proLOG on the screw heads, and then pull
down. Now secure the Powador-proLOG with a third screw in
the lower part of the unit.
Page 10 10
-
+
-
+
+
-
Drill hole sketch (lengths in mm)
92
110
220
5.3

Connections

Powador-proLOG S
Powador-proLOG M/L/XL

5.3.1 Voltage supply

The Powador-proLOG is powered by an integrated power
supply. The grid connection (230  V) should be protected by
a fuse (e. g. B6A). The power supply provides 24  V, e. g. to
power a solar sensor.
Powador-proLOG S