Viessmann VITODENS 200 Start-Up And Service Instructions page 24

Wb2 series wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for VITODENS 200:
Table of Contents

Advertisement

Initial Start-up and Service
Steps
(continued)
S
ervice
B
D
A C
I
nitial start-up
24
25. Measure ionization current
IMPORTANT
Switch off heating system on
the control unit before connecting the
measuring instrument.
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Connect a DC μA multimeter in
series with the ionization cable as
follows:
a)Disconnect the socket of the
ionization cable
from the
ionization electrode
connect to the plug of the
multimeter via adaptor
b)Connect additional ionization
measuring cable
to the
ionization electrode
socket of the multimeter.
3. Start up boiler to its maximum input:
Turn emissions test switch "S" on
the control unit to "h".
4. If the ionization current is less than
5 μA
H check the electrode clearance (see
page 20).
H check the power supply
connection of the control unit.
5. After completing the measurement,
turn emissions test switch to "a".
6. Enter the value measured in the
Maintenance Record on page 70 in
this manual.
26. Verify programming unit system coding addresses
The control unit must be adjusted according to the system equipment. See
H page 48 onwards for programming unit.
For details on coding procedure and for an overview of the coding addresses, see
H page 50 onwards for programming unit.
Please note:
The measurement can be made with
a multimeter (measuring range 0 to
100 μA).
and
.
and the
Please note:
The minimum ionization current must
be at least 5 μA when the flame is
formed (approx. 2-3 seconds after
opening the gas combination valve).