Disassembly Procedure - Mitsubishi Electric PAC-MK50BC Technical And Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PAC-MK50BC:
Table of Contents

Advertisement

8

DISASSEMBLY PROCEDURE

BRANCH BOX : PAC-MK50BC
OPERATING PROCEDURE
1. Removing the controller cover and under panel
(1) Remove 3 controller cover fixing screws (4 o 10) to detach
the controller cover. (See Photo 1)
(2) Remove 4 under panel fixing screws (4 o 10) to remove
the under panel. (See Photo 1)
2. Removing the thermistor (TH-A–E*)
(1) Remove the controller cover. (See Photo 1)
(2) Remove the under panel. (See Photo 1)
(3) Remove 8 insulations, then remove 9 pipe box (under) fix-
ing screws (4 o 10). (See Photo 2-1)
(4) Pull out the thermistor(s), TH-A–E, from the sensor hold-
ers mounted on the gas pipe. (See Photo 2-2)
(5) Loosen the insulation sheet which bundles the thermistor
connectors.
(6) Loosen the side clamps, then disconnect the connector(s)
on the controller board.
(7) Pull out the lead wire(s) through the hole to the controller
board side.
*TH-A–C for PAC-MK30BC. (See Photo 2-3)
Photo 2-3
Header assy
LEV assy
hole
Insulation sheet
OCH574
PAC-MK30BC
Sensor holder
Rubber mount
Band
PHOTO : PAC-MK50BC
PHOTOS
Photo 1
Under panel fixing screws
Under panel
Controller cover
fixing screws
Photo 2-1
Pipe box (under) fixing screws
Pipe box
(under)
Screw
Insulations
(15 x 15 x 46)
Photo 2-2
Sensor holder
LEV assy
Header assy
hole
24
Controller cover
fixing screw
Controller cover
Screws
Insulations
(15 x 12 x 45)
Rubber mount
Band
Insulation sheet