Var Limiter - Basler DECS-250 Instruction Manual

Digital excitation
Hide thumbs Also See for DECS-250:
Table of Contents

Advertisement

A
Stator Current Limiter Enable: Check box to enable.
B
Low SCL Level: Adjustable from 0 to 66,000 Aac in 0.1 Aac increments.
C
High SCL Level: Adjustable from 0 to 66,000 Aac in 0.1 Aac increments.
D
High SCL Time: Adjustable from 0 to 60 s in 0.1 s increments.
E
Initial Delay: Adjustable from 0 to 10 s in 0.1 s increments.

Var Limiter

BESTCOMSPlus
HMI Navigation Path: Settings, Operating Settings, Limiters, VAR
The var limiter can be enabled
and secondary setting groups provide additional control for two distinct machine operating conditions. The
var limiter setpoint
A delay setting
acts to limit the var flow.
Var limiter settings are illustrated in Figure 52.
A
Var Limiter Enable: Select checkbox to enable var limiter.
B
Var Limiter Setpoint: Adjustable from 0 to 200% in 0.1% increments.
C
Var Limiter Delay: Adjustable from 0 to 300 s in 0.1 s increments.
CALL US TODAY
CALL US TODAY
1-888-POWER-58
1-888-POWER-58
Figure 51. Stator Current Limiter Settings
®
Navigation Path: Settings Explorer, Operating Settings, Limiters, var
A
to limit the level of reactive power exported from the generator. Primary
B
is expressed as a percentage of the calculated, maximum VA rating for the machine.
C
establishes a time delay between when the var threshold is exceeded and the DECS-250
Figure 52. Var Limiter Settings