Important Information - EA Technology UltraTEV Plus2 Operating Manual

Table of Contents

Advertisement

EA Technology UltraTEV Plus
3.

Important Information

For application information please contact:
product-support@eatechnology.com
Operating Manual
2
The UltraTEV Plus
is designed for use at ground potential only.
2
When testing electrical plant ensure that the metalwork is earthed
before taking any measurements.
Maintain safety clearances between structures at high voltage and
the instrument, its probes and the operator at all times.
RFCTs, connecting leads and test equipment do not provide
protection against high voltage.
Under no circumstances are earth/ground connections to be
loosened, disconnected or otherwise altered to allow use of this
equipment.
Adhere strictly to local safety procedures.
Do not make measurements when there are electrical storms in the
vicinity.
Do not make measurements immediately following the energisation
of a circuit.
Do not disturb plant during measurements either mechanically (e.g.
by shaking or striking it), electrically (e.g. by increasing the voltage)
or physically (e.g. by applying heat).
Do not operate the instrument or its accessories in an explosive
atmosphere.
Mains supply voltages are present within the battery charger.
This unit contains no user serviceable parts, always return to EA
Technology or your local distributor for service and repair.
Care must be taken where work is performed in tight corners, where
the proximity of other earth planes will affect the reading. If
possible maintain a distance of more than 30cm from metal work
which runs perpendicular to the sensor faceplate.