Measure Screen - EA Technology UltraTEV Plus2 Operating Manual

Table of Contents

Advertisement

EA Technology UltraTEV Plus

5.6.1 Measure Screen

The Measure mode is common to both TEV and Cable PD. This mode displays TEV readings
in dBmV (dB) or (if the RFCT accessory is connected) Cable PD readings in picoCoulombs
(pC).
To enter this mode, click the Measure icon
P/Cycle – Shows the pulses per cycle based on either a 50 or 60Hz mains
frequency.
Severity – Shows the short term severity (calculated by multiplying TEV magnitude
(mV) by Pulses Per Cycle). When in Cable PD mode, this is calculated by Charge
(pC) multiplied by Pulses Per Cycle.
Max dB – displays the maximum dB value registered by the UltraTEV Plus
screen was entered or paused/reset. This value is displayed in pC.
Chart - The bar chart is used to show the amplitude of the current values being
read by the UltraTEV Plus
Noise Level – This displays the amplitude in dB of the background noise level.
To exit the TEV screen back to the main menu, press the Home button
There is an option to record a reading, this can be done by either clicking the red record
icon on the screen
a 'survey' detailed in a later section of this manual.
Pausing a reading can also be achieved by either presing the Right button or clicking on
the 'Pause'
icon. Audio output is also muted during a pause operation. After pausing
the screen the measurment can be restarted by pressing the restart button.
Operating Manual
2
, from right to left.
2
or by pressing the Middle button
Page 13 of 66
.
. All recordings are stored within
2388L015
since the
2
.

Advertisement

Table of Contents
loading

Related Products for EA Technology UltraTEV Plus2

Table of Contents