Procedure For Power Supply Wiring - Daikin CONVENI-PACK Installation Manual

Hide thumbs Also See for CONVENI-PACK:
Table of Contents

Advertisement

Available languages

Available languages

• When passing electrical wiring through the knock holes, protect
the wiring with a conduit or bushings, making sure not to damage
the wiring.
• If small animals might enter the unit, block off any gaps (hatching
parts) with material (field supply).
Knockout hole
(For low-voltage wiring)
Knockout hole
(For high-voltage wiring)

7-3 Procedure for Power Supply Wiring

¢Procedure for Power Supply Wiring²
1
2
B
3
5
6
1 Power supply (3 phase 380~415)
2 Overcurrent circuit breaker (earth leakage circuit breaker), all pole
disconnection switch
3 Earth wire
4 Power supply terminal block
5 Mount insulation sleeves
6 Fix the power supply wiring for phases L1, L2, L3, and N, respec-
tively, with the provided clamp (1) to the resin clamp.
7 Fix the earth wire to the power supply wire (phase N) with the pro-
vided clamp (1).
8 Earth wire
Perform wiring so that the earth wire will not come in contact with
lead wires of the compressor. Otherwise, noise generated may
have a bad influence on other equipment.
9 Ground terminal
10 • When two wires are connected to a single terminal, connect
them so that the rear sides of the crimp contacts face each
other.
• Also, make sure the thinner wire is on top, securing the two
wires simultaneously to the resin hook using the accessory
clamp (1).
Crip style terminal
Terminal block
12
Burr
4
10
L 1
L 2
L 3
N
9
8
7
Clamp (1)
Wire: narrow
Wire: thick
Resin hook
Power circuit, safety device, and cable requirements (X1M~X4M
terminal block)
• A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase
and an earth leakage circuit breaker.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (1 second or less) 200mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
relevant local and national regulations.
• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.
• Use wire type H07RN-F when protected pipes are not used.
Phase and
frequency
I3, 50Hz
LRYEQ16AY1
Point for attention regarding quality of the public electric power
supply
This equipment complies with respectively:
„ EN/IEC61000-3-11
(1)
provided that the system impedance Z
less than or equal to Z
and
max
(2)
„ EN/IEC61000-3-12
provided that the short-circuit power S
greater than or equal to the minimum S
at the interface point between the user's supply and the public sys-
tem. It is the responsibility of the installer or user of the equipment to
ensure. by consultation with the distribution network operator if nec-
essary, that the equipment is connected only to a supply with respec-
tively:
„ Z
less than or equal to Z
sys
max
„ S
greater than or equal to the minimum S
sc
Z
(:)
max
LRYEQ16AY1
0.24
(1) European/International Technical Standard setting the limits for
voltage changes.
Voltage llucruations and flicker in public low-voltage supply sys-
tems for equipment with rated current d 75A
(2) European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current > 16A and d 75A per
phase.
Operation output wiring connections
• Connect operation output wiring to the X2M terminal block and
clamp as indicated by the following diagram:
X2M wire specifications
Electric wire thickness
Max. wiring length
Minimum
Recom-
Voltage
circuit
mended
amp.
fuses
380-415V
35.2A
40A
sys
is
sc
value
sc
and
value.
sc
minimum S
value
sc
1038KVA
Clamp (1)
2
0.75~1.25mm
130m
English
is