Unit Mounting – Install the steam humidifier so that the minimum bend radius R=12" / 300mm for Nortec hose, R=5 x internal diameter for hard pipes and upslope (min 10º) / downslope (min 2º) of the steam hose is maintained. –...
The water drain is to be carried out according to the figure found in and the applicable local regulations for water installation. Section 5.6.1 of the RS Series Installation Manual, 2582419 and the applicable local regulations for water installations. The The indicated connection specifications must be observed.
– The steam line should be kept as short as possible, as per Table will cause an excessive increase in pressure in the steam cylinder when 1 from the RS Series Installation Manual (2582419). Ensure the the unit is operating and could lead to the risk of scalding accidents. All the minimum bend radii are observed: 12"...
Electrical Connection For wiring diagram of double tank humidifier, refer to Installation Manual (2582419).
Page 8
2578999-A | November 19, 2015 Nortec Humidity Ltd. does not accept any liability for any damage caused by faulty installation or the use of components that are not approved 835 Commerce Park Drive Ogdensburg, NY 13669 EMAIL: nortec@humidity.com...