ADDITIONAL REFRIGERANT CHARGE
CAUTION
• Refrigerant may only be charged after performing
the leak test and the vacuum pumping.
• Check the type of refrigerant to be used on the
machine nameplate. Charging with an unsuitable
refrigerant may cause explosions and accidents,
so always ensure that the appropriate refrigerant
is charged.
• Refrigerant containers shall be opened slowly.
• The outdoor unit is factory charged with
refrigerant. Calculate the added refrigerant
according to the diameter and the length of
the liquid pipe of the outdoor unit/indoor unit
connection.
Pipe length and refrigerant amount:
Air
Additional amount of refrigerant
Connective
purging
pipe length
to be charged
method
Less
Use
than 7.5m
vacuum
pump.
/295.3"
More
Use
than 7.5m
vacuum
pump.
/295.3"
• Be sure to add the proper amount of additional
refrigerant. Failure to do so may result in reduced
performance.
REFRIGERANT PIPING WORK
• Caution on the pipe handling, protect the open
end of the pipe against dust and moisture. All pipe
bends should be as gentle as possible. Use a pipe
bender for bending.
Rain
Be sure to
place a cap.
If no flare cap is
available, cover the
flare mouth with
tape to keep dirt or
water out.
Liquid side: 6.35mm/.25"
R410A: (Pipe length-7.5(25))
x15g/m(0.16oz/ft)
Liquid side:
9.52mm/.375"
R410A: (Pipe length-7.5(25))
x30g/m(0.32oz/ft)
• Be sure to insulate both the gas and liquid piping.
Use separate thermal insulation pipes for gas and
liquid refrigerant pipes. See the figure below.
Gas pipe
Gas pipe
insulation
Finishing tape
• Finally, insulate as shown in the figure below.
6
5
3
1
2
4
PIPING INSULATION PROCEDURE
Gas piping
1
6
3
2
A
C
1 Piping insulation material (field supply).
2 Flare nut connection.
3 Insulation for fitting (field supply).
4 Piping insulation material (main unit).
5 Indoor unit.
6 Clamp (field supply).
A Turn seams up.
B Attach to base.
C Tighten the part other than the piping insulation
material.
WARNING
Wall
• For local insulation, be sure to insulate local
piping all the way into the pipe connections
inside the unit. Exposed piping may cause
condensation or may cause burns when touched.
• Make sure that no oil remains on plastic parts of
the decoration panel (optional equipment). Oil
may cause degradation and damage to plastic parts.
bn
Inter-unit wire
Liquid pipe
Liquid pipe
insulation
Drain hose
1 Liquid pipe
2 Gas pipe
3 Insulation for liquid pipe fitting
4 Insulation for gas pipe fitting
5 Clamps
(use 2 clamps per insulation)
6 Indoor unit
Liquid piping
6
4
5
1
6
3
2
B
A
C
6
4
5
B