Chigo SA-ZM03ENG-1 Instruction Manual page 11

Full dc inverter celling-mounted cassette type
Table of Contents

Advertisement

When there are barriers at front side and
both sides, do not use the dimensions
shown in the figure. Please refer to the
right figure
2. Multi unit installation (unit: mm)
A. Parallel setting
Above 500
Above 300
B. Multi-row arrangement
Above 5000
3.Preparation before installation
When there are barriers at front side and
back side, at the location with barrier and
poor air ventilation, to avoid short circuit of
outdoor unit inlet and outlet, the heights and
widths of barriers shall be within following
range. (If its front side and back side can
meet the condition, it will be no special limit
for both sides. )
A. Barrier width is 1.5 times less than
outdoor units
B. Barrier width is 1.0 times less than
outdoor units
When there are barriers around, even if
the upward side is open, it can not
installed.
Below 10 pcs
9
As shown in the figure, ensure
the maintenance space at front
of unit
Maintenance space
Above 500
Above 1500
C. Blowing arrangement
Above 5000
Above 500