Siemens Simatic S7-1500 Manual page 19

Digital output module dq 8x230vac/2a st triac
Hide thumbs Also See for Simatic S7-1500:
Table of Contents

Advertisement

Meaning of the LED displays
The following table explains the meaning of the status and error displays.
RUN and ERROR LED
Table 5- 1
Status and error displays RUN and ERROR
LED
RUN
ERROR
Off
Off
Off
Flashes
On
Off
Flashes
Flashes
CHx LED
Table 5- 2
CHx status display
LED CHx
Off
On
Digital output module DQ 8x230VAC/2A ST Triac (6ES7522-5FF00-0AB0)
Manual, 09/2016, A5E03485733-AD
Meaning
Voltage missing or too low at backplane bus
The module starts and flashes until the valid
parameter assignment is set.
Module is configured
Hardware defective
Meaning
0 = Status of the output signal
1 = Status of the output signal
5.1 Status and error displays
Remedy
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Replace the module.
Remedy
---
---
Diagnostic alarms