Storm Collar Installation (SC1)
Place storm collar over pipe and slide down until it is snug against
open edge of lashing (see Figure 14). Use SC1 for all round termina-
tions. Apply waterproof caulk around perimeter of collar to provide
a proper seal.
Chimney
Pipe
Storm
Collar
Figure 14 - Storm Collar
Terminations/Spark Arrestor
Fireplace system must be terminated with listed round top or chase
terminations. In any case, refer to installation instructions supplied
with termination. Terminations approved for this fireplace are RT-
8DM and RLT-8DM that can be used for lashing or chase and ET-
8DM, ETO-8DM, ETL-8DM and ETLO-8DM for chase style termination
only. Figure 18 shows an RLT-8DM round top termination.
CAUTION: Do not seal openings on the rooftop
lashing. Follow the installation instructions provided
with the termination being used.
Terminations with 16" slip pipe sections are available. RTT-8DM,
RTTL-8DM and RLTT-8DM are approved for flashing installations.
When needed, these adjustable terminations may be used in combi-
nation with pipe assembly to achieve correct chimney height.
Note: In the rare instance there is a problem with side driven rain or
wind or chimney is not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
Figure 15 - Termination
127055-01E
VENTING INSTALLATION Continued
Waterproof
Caulk
Flashing
RLT-8DM
Level of Flue
Gas Outlet
Flue Pipe
of RLT-8DM
Inside Inner
Pipe of
Chimney
Caulk
Collar
Flashing
Underlap Shingles
Bottom Only
Superiorfireplaces.US.com
CHASE INSTALLATIONS
Instructions for chase installations are included with chase style ter-
mination chosen. In a multiple chase installation, be sure to provide
adequate distance between terminations to prevent smoke spillage
from one termination to another. We suggest that terminations be
separated at least 24", center to center and stacked at a vertical height
difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed, contact manufacturer
for specifications.
24" Min.
24" Min.
Figure 16 - Multiple Chase Installation
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of
3 feet in height above highest point where it passes through roof and
must be at least 2 feet above highest point of the roof that is within
a horizontal distance of 10 feet (see Figure 17).
10'
2' Min.
Figure 17 - 10 Foot Rule
FINISHING FIREPLACE
Combustible materials, such as wallboard, sheet rock, drywall, ply-
wood, etc., may make direct contact with sides and top around fire-
place face. It is important that combustible materials do not overlap
face itself. Brick, glass, tile or other noncombustible materials may
overlap front face provided they do not obstruct essential openings
such as louvered slots. When overlapping with a noncombustible
facing material, use only noncombustible mortar or adhesive.
18"
Min.
Level of
Flue Gas
Outlet
10'
3' Min.
2' Min.
3' Min.
11