4.2
Installing and Operating the PB-16 Actuator
STEP 1 – Be sure the magnet is in the OFF position.
STEP 2 – Determine which slots that the plunger should be in for your application and
adjust plunger to those slots. Also, determine the starting height of the plunger and
tightened the thumbscrews.
Generally, if you have a button that extends from your switchgear door, you will need to
slide the plunger to be closer to the 1.40" height so that it can clear the button. If you
have a recessed button, you may find that the lower setting of 0.30" works best as it
allows the most stroke below the switchgear surface. See Section 4.1 for more
information on mounting dimensions and adjustability.
The actuator can be positioned in one of the
two sets of slots to best align the plunger
over your button.
© MarTek Limited. All rights reserved.
PB16 Operating Manual
PB16‐033117 v0
Position the actuator within the
slots to best align the plunger
height to your button and
tighten the thumbscrews.
6