The magnet should be firmly against the switchgear door. If the magnet is not set
firmly against the door, it will likely not have enough holding power to stay on the
door when actuated.
STEP 5 – When ready to operate, stand away at a safe distance, turn the power switch
on the hand-held controller to the ON position, hold the "ENABLE" button, and push and
hold the "ACTIVATE" button on the controller to extend the plunger. Release the button
and the plunger will retract.
The green "Enabled" LED should light when the "ENABLE" button is held. The "Moving"
LED should light when the actuator is being commanded to move. If the battery voltage
is low, the yellow "Low Bat" LED will flash and the actuator will not operate.
The LED on the actuator will light "Red" when it is extending and "Green" when it is
retracting.
4.2
Removing the PB-16 Actuator
STEP 1 – Firmly hold onto the PB-16 actuator.
STEP 2 – Turn the magnet lever counter-clockwise to the OFF position.
STEP 3 – The actuator can now be moved away from the door.
Do not attempt to remove the actuator without turning the magnet OFF. Doing so
can be difficult and dangerous.
5.0
Storage
The PB-16 is provided with a heavy duty carrying case that can be used to conveniently store the
actuator and its necessary components. The carrying case and complete unit should be stored in a clean
and cool environment.
If it is stored for longer than 30 days without being used, the batteries should be removed.
.
© MarTek Limited. All rights reserved.
PB16 Operating Manual
PB16‐033117 v0
8