E T C I n s t a l l a t i o n G u i d e
Automatic Load Control Relay
Step 1:
Step 2:
Step 3:
EMERGENCY POWER IN
EMERGENCY NEUTRAL
Reference
N o t e :
Step 4:
Step 5:
N o t e :
Step 6:
Step 7:
Au toma tic Loa d C ontro l R ela y
Locate the normal and emergency circuit breaker panels and turn off the power
to the circuits.
Remove face plates and other hardware from the junction box, gaining access to
the high voltage wiring.
The ALCR-PP mounts to the exterior of the junction box or panel with the
1/2" threaded nipple. Attach the unit to the junction box.
(
12
)
BLACK
AWG
EMERGENCY POWER OUT
(
12
)
RED
AWG
(
18
)
GRAY
AWG
A
L
UTOMATED
C
R
ONTROL
ELAY
(ALCR-PP)
Remote
LED
"Examples of Use" on page 8
Follow all local code requirements for terminating wiring. Notice the harness
wires on the controller unit are pre-stripped for your installation convenience.
Connect the Emergency power wiring leads.
a:
Connect the Emergency Power In and Power Out wiring leads (Black 12
AWG and Red 12 AWG) on the ALCR-PP with the emergency lighting loads
as shown in the above wiring diagram.
b:
Connect the Emergency Neutral (Gray 18 AWG) for the emergency circuit
to the Emergency Neutral lead as shown.
Connect the Normal sense wiring leads.
a:
Connect the Normal Power Sense (Black 18 AWG) and Normal Switch
Sense (Red 18 AWG) wiring leads to the normal lighting circuit as shown.
To ensure the emergency lighting in the controlled area turns On in the event
of a power loss, you must connect the Normal Power Sense wires on the line
side of (before) any switched control device for the normal lighting loads.
b:
Connect the Normal Neutral (White 18 AWG) lead to the normal Neutral for
the lighting loads.
Proceed to
"Initial Test" on page
If you are installing a remote triggering device to remotely activate the emergency
circuit, refer to
"Installing a Remote Activation Input to the ALCR-PP"
instructions.
P age 3 of 8
NORMAL POWER SENSE
NORMAL SWITCH SENSE
NORMAL NEUTRAL
OAD
Option
Button
for possible installation layouts.
7.
(
18
)
BLACK
AWG
(
) 18
RED
AWG
(
18
)
WHITE
AWG
Status
LED
E le ctron ic The atre Co ntrol s, Inc .
:
NORMALLY CLOSED
TEST SWITCH
FIRE ALARM PANEL
SECURITY SYSTEM
for wiring