FLUE RESISTANCES
FLUE SYSTEMS
For concentric flue systems with elbows fitted, use the table to correct the maximum flue extension capability.
Alternatively use the table to design the flue system, deducting the individual resistance of components from
the maximum pressure drop allowed in the flue for that boiler. The maximum pressure drop allowed in the flue is
given below.
PERMISSIBLE FLUE LENGTH
The maximum permissible flue lengths for each model are shown in Table 1 below, these lengths are inclusive of
the terminal resistance. The value shown is the maximum available length for extension. The equivalent length of
elbows is shown in Table 2.
TABLE 1
MAX PERMISSIBLE EQUIVALENT FLUE LENGTH
(INC TERMINAL RESISTANCE) METRES
CONCENTRIC
Flue Size 80/125
100/150
Model
30/30P
42
-
40/40P
52
-
60/60P
7.5
30
80/80P
12
35
100
-
14.3
120
-
17.6
150
-
7.5
MAX
PERMISSIBLE
MODEL
FLUE TYPE
EQUIVALENT
LENGTH
(TABLE 1)
60
80/125
7.5
60
100/150
30
80
80/125
12
120
100/150
17.6
TABLE 2
OPEN FLUE
Size
80
100
45˚
90˚
65
-
70
-
25
-
22
-
-
20
-
49
-
32
EXAMPLES OF FLUE LENGTH CALCULATION
EQUIVALENT
TYPE
LENGTH
(TABLE 2)
90
1.6
90
1.9
90
1.6
90
1.9
EQUIVALENT LENGTH OF ELBOWS (METRES)
CONCENTRIC
80/125
100/150
0.85
1.25
1.6
1.9
ELBOWS
TOTAL
NO
EQUIVALENT
LENGTH
2
3.2
2
3.8
3
4.8
4
7.6
OPEN FLUE
80
100
0.45
0.60
1.0
1.0
MAX
PERMISSABLE
STRAIGHT
LENGTH
4.3
26.2
7.2
10.0
31