Dielectric voltage withstand
Impulse voltage withstand
Insulation resistance
Electrostatic Discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25 Class A
Power magnetic Immunity
Pulsed Magnetic Immunity
Damped Oscillatory magnetic
Voltage Dip & interruption
Damped Oscillatory
Ingress Protection
1–12
Courtesy of NationalSwitchgear.com
TYPE TESTS
TEST
REFERENCE STANDARD
EN60255-27
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-8
IEC61000-4-9
IEC61000-4-10
IEC61000-4-11
IEC60255-11
IEC61000-4-18/IEEEC37.90.1
IEC60529
APPROVALS
Applicable Council Directive
Low voltage directive
CE compliance
EMC Directive
(Standard Version,
Mod 502, 504, 505,
506, 512)
LVD Directive
North America
cULus e83849 NKCR/7
cUlus e234799 NOIV/NOIV7
Manufactured under a
ISO
registered quality program
ENVIRONMENTAL
Ambient temperatures:
Operating range:
Altitude:
Insulation:
Pollution Degree:
Overvoltage Category:
Ingress protection:
2300VAC
5KV
500VDC >100mohm
Level 4
10V/m 80-1Ghz,1.4-2.7Ghz +spot
Class B
2Kv & 1KV
10Vrms
Level 5
1000A/m
100A/m
0,40,70,80% dips,250/300cycle interrupts
DC interrupts and ripple (15%)
2.5KV @1Mhz 100Khz
IP40 front, IP10 back
According to:
EN60255-27 (normative)
EN61000-6-2, EN50263 Zone B
EN61000-6-4
EN60255-27
UL508/C22.2.No 14
Haz loc Class1 Div 2 (Mod 513)
ISO9001
-10C to 60C
2000m (max)
Class 1
II
II
IP40 Front
IP10 Back
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW
TEST LEVEL