GE Digital Energy Multilin 239 Instruction Manual page 18

Motor protection relay
Table of Contents

Advertisement

Dielectric voltage withstand
Impulse voltage withstand
Insulation resistance
Electrostatic Discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25 Class A
Power magnetic Immunity
Pulsed Magnetic Immunity
Damped Oscillatory magnetic
Voltage Dip & interruption
Damped Oscillatory
Ingress Protection
1–12
Courtesy of NationalSwitchgear.com
TYPE TESTS
TEST
REFERENCE STANDARD
EN60255-27
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-8
IEC61000-4-9
IEC61000-4-10
IEC61000-4-11
IEC60255-11
IEC61000-4-18/IEEEC37.90.1
IEC60529
APPROVALS
Applicable Council Directive
Low voltage directive
CE compliance
EMC Directive
(Standard Version,
Mod 502, 504, 505,
506, 512)
LVD Directive
North America
cULus e83849 NKCR/7
cUlus e234799 NOIV/NOIV7
Manufactured under a
ISO
registered quality program
ENVIRONMENTAL
Ambient temperatures:
Operating range:
Altitude:
Insulation:
Pollution Degree:
Overvoltage Category:
Ingress protection:
2300VAC
5KV
500VDC >100mohm
Level 4
10V/m 80-1Ghz,1.4-2.7Ghz +spot
Class B
2Kv & 1KV
10Vrms
Level 5
1000A/m
100A/m
0,40,70,80% dips,250/300cycle interrupts
DC interrupts and ripple (15%)
2.5KV @1Mhz 100Khz
IP40 front, IP10 back
According to:
EN60255-27 (normative)
EN61000-6-2, EN50263 Zone B
EN61000-6-4
EN60255-27
UL508/C22.2.No 14
Haz loc Class1 Div 2 (Mod 513)
ISO9001
-10C to 60C
2000m (max)
Class 1
II
II
IP40 Front
IP10 Back
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW
TEST LEVEL

Advertisement

Table of Contents
loading