Loading Setpoints from a File
An error message will occur when attempting to download a setpoint file with a
revision number that does not match the relay firmware. If the firmware has been
upgraded since saving the setpoint file, see Upgrading Setpoint Files to a New Revision
on page 6–82 for instructions on changing the revision number of a setpoint file.
The following procedure illustrates how to load setpoints from a file. Before loading a
setpoints file, it must first be added to the EnerVista 239 Setup environment as described
in Adding Setpoints Files to the Environment on page 6–80.
 Select the previously saved setpoints file from the File pane of the
EnerVista 239 Setup software main window.
 Select the File > Properties menu item and verify that the
corresponding file is fully compatible with the hardware and
firmware version of the target relay.
If the versions are not identical, see Upgrading Setpoint Files to a
New Revision on page 6–82 for details on changing the setpoints file
version.
 Right-click on the selected file.
 Select the Write Settings to Device item.
 Select the target relay from the list of devices shown.
 Click Send.
If there is an incompatibility, an error will occur: If there are no
incompatibilities between the target device and the settings file, the
data will be transferred to the relay. An indication of the percentage
completed will be shown in the bottom of the main window.
CHAPTER 6: User Interface
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL