Customer Guidance - Fujitsu AGYG09LVCA Installation Manual

Indoor unit floor type
Hide thumbs Also See for AGYG09LVCA:
Table of Contents

Advertisement

After turning off the power, wait 10 seconds or more before turning on it again.
The Function Setting does not become active unless the power is turned off then on
again.
Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the fi lter. Select the
time setting for the fi lter sign display interval in the table below according to the amount
of dust or debris in the room. If you do not wish the fi lter sign to be displayed, select the
setting value for "No indication".
Setting Description
Standard (400 hours)
Long interval (1,000 hours)
Short interval (200 hours)
No indication
Setting vane
When embedding the indoor unit in a wall, restrict the movement of the horizontal vane for
the upper air outlet so that it only operates horizontally.
If this setting is not performed, heat will build up in the wall and the room will not be cooled
or warmed properly.
Setting Description
Standard
(Setting forbidden)
In a wall
Cooling Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
Setting Description
Standard
Slightly lower control
Lower control
Warmer control
Heating Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
Auto Restart
Enable or disable automatic system restart after a power outage.
Setting Description
Yes
No
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the Wired remote controller temperature
sensor.
En-9
AMP Air Conditioning
CAUTION
(♦... Factory setting)
Function Number
Setting Value
00
01
11
02
03
(♦... Factory setting)
Function Number
Setting Value
00
23
01
02
(♦... Factory setting)
Function Number
Setting Value
00
01
30
02
03
(♦... Factory setting)
Function Number
Setting Value
00
01
31
02
03
(♦... Factory setting)
Function Number
Setting Value
00
40
01
Setting Description
No
Yes
* If setting value is "00" :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is "01" :
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
Setting Description
A
B
C
D
External input control
"Operation/Stop" mode or "Forced stop" mode can be elected.
Setting Description
Operation/Stop mode
(Setting forbidden)
Forced stop mode
Setting record
Record any changes to the settings in the following table.
Setting Description
Filter sign
Cooler room temperature correction
Heater room temperature correction
Auto restart
Indoor room temperature sensor switching function
Remote controller signal code
External input control
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.

13. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
fl ow switching, and other remote control unit operations.
(2) Air fi lter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.
www.ampair.co.uk | sales@ampair.co.uk
(♦... Factory setting)
Function Number
Setting Value
00
42
01
(♦... Factory setting)
Function Number
Setting Value
00
01
44
02
03
(♦... Factory setting)
Function Number
Setting Value
00
46
01
02
Setting Value