Mounting Suction Grille · Decoration Side Panel; Field Setting - Daikin FHA35AVEB Installation Manual

Hide thumbs Also See for FHA35AVEB:
Table of Contents

Advertisement

(2) Connect crossover wiring between the terminals (P1, P2)
inside the control box for the remote controller. (There is no
polarity.) (Refer to Fig. 34 and Table 3)
Terminal for remote
controller wiring (P1, P2)
Indoor unit 1
Terminal block
Crossover wiring
Control with 2 remote controllers control
Power supply
Earth
220 - 240V
leakage
~
breaker
50Hz
Outdoor unit
1 2 3
NOTE)
1 2 3
P1 P2
Indoor unit
Remote
Remote
controller
controller
(Optional
(Optional
P1 P2
P1 P2
accessory)
accessory)
Two remote controllers control (Controlling 1 indoor unit
by 2 remote controllers)
• When using 2 remote controllers, one must be set to "MAIN"
and the other to "SUB".
MAIN/SUB CHANGEOVER
• Refer to the manual attached to the remote controller.
Wiring Method
(1) Remove the control box cover.
(2) Add wiring between the remote controller 2 (Sub) and the
terminal (P1, P2) of the terminal block (X1M) for the remote
controller in the control box. (There is no polarity.)
Remote
controller 1
(Main)
* For simultaneous operation system, be sure to
connect the remote controller to the master unit.
NOTE
NOTE
NOTE
NOTE
• Terminal numbers of outdoor and indoor units must be
matched.
English
Indoor unit 2
(Master)
(X1M)
P1
P2 F1
F2
to next unit
Terminal block
(X1M)
Fig. 35
Indoor unit
(Slave)
Outdoor unit
Indoor unit
(Master)
Remote
controller 1
controller 2
(Optional
(Optional
accessory)
accessory)
Fig. 36
Terminal block
(X1M)
( Master *)
Additional
remote controller
Remote
controller 2
(Sub)
10.
MOUNTING SUCTION GRILLE · DECORATION SIDE
PANEL
Install securely in the reverse order when decoration side panel
and suction grille were removed.
• When installing the suction grille, hang the string of the suc-
tion grille to the hanging part of the indoor unit shown Fig. 38.
CAUTION
When closing the suction grille, the strap may get caught.
Confirm that the strap does not stick out of the side of the
suction grille before closing.
Round hole
Indoor unit
Suction grille
11.

FIELD SETTING

<<Refer to also the installation manual attached to the out-
Remote
door unit.>>
CAUTION
Before carrying out field setting, check the items mentioned
in the clause 2 "1. Items to be checked after the installation
work is completed" on page 3.
• Check if all the installation and piping works for the air
conditioner are completed.
• Check if the control box cover of air conditioner is closed.
<FIELD SETTING>
<After turn on the power supply, carry out field setting from the
remote controller according to the installation state.>
• Carry out setting at 3 places, "Mode No.", "FIRST CODE No."
and "SECOND CODE No.".
The settings shown by "
when shipped from the factory.
• The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note)Though setting of "Mode No." is carried out as a group,
if you intend to carry out individual setting by each
indoor unit or confirmation after setting, carry out set-
ting with the "Mode No." shown in the parenthesis ( ).
• In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
[1] Enter into the field setting mode with the remote controller.
[2] Select Mode No. "12".
[3] Set the FIRST CODE No. to "1".
[4-1] For FORCE OFF, set the SECOND CODE No. to "01".
[4-2] For ON/OFF OPERATION, set the SECOND CODE No.
to "02".
(It is set to FORCED OFF when shipped from the factory.)
• Ask your customer to keep the manual attached to the
remote controller together with the operation manual.
• Do not carry out setting other than those shown in the table.
Fig. 37
11-1
SETTING WHEN AN OPTIONAL ACCESSORY IS
ATTACHED
• For setting when attaching an optional accessory, refer to the
installation manual attached to the optional accessory.
Round hole
Strap
Hook
Cross hole
Fig. 38
" in the table indicate those
Hook
Strap
15

Advertisement

Table of Contents
loading

Table of Contents