Rheem RGPE series Installation Instructions Manual page 51

2 stage, 80+ gas furnaces
Table of Contents

Advertisement

When the system has found all neces-
sary components, the text area of the
communicating thermostat will go blank.
This is an indicator that the system is
operating properly. Proceed by engag-
ing a typical thermostat call to determine
if operation is correct as described in
the section of this book titled START UP
PROCEDURES" to test heating, cooling
and fan operation and to make neces-
sary adjustments.
NOTE: When a communicating con-
denser is installed with the system, a
capital "C" will be displayed at the fur-
nace seven-segment display for both
low & high cooling stages.
CONTINUOUS FAN OPERATION IN
C C O O M M M M U U N N I I C C A A T T I I N N G G M M O O D D E E
Continuous fan operation will always
depend on the selection (Hi, Med, Low)
made at the communicating thermostat
for the continuous fan speed (see instal-
lation instructions for the thermostat).
However, during the first few operations
of continuous fan, the blower speed will
be limited to a maximum of 600 CFM for
1
HP motors (75KBTU), 700 CFM for
2
3
HP (75KBTU (wide) and 50 KBTU)
4
and 1000 CFM for 1 HP motors
(100KBTU). This will continue until the
high cooling call information is provided
from the condenser. Once the max cool-
ing CFM value has been transmitted by
the condenser (condenser must reach
high stage – in heat pump or cooling),
the continuous fan will then have a max-
imum CFM value equal to the max cool-
ing airflow from the condenser. The Hi,
Med and Low selections for continuous
fan will be based on max CFM of the
condenser with Hi continuous fan speed
equal to the high speed CFM of the
cooling/HP condenser.
NOTE: When default values are reset in
the furnace "SETUP" user menu, the
continuous fan CFM will be restored to
factory default (Max = 600 CFM for
3
HP, 700 CFM for
HP and 1200 CFM
4
for 1 HP). These values will again be
used to calculate continuous fan airflow
until a cooling call has been established
and a communicating condenser sends
a fan demand to the furnace control.
ACTIVE FAULT CODES WITH COM-
MUNICATING SYSTEMS
Two levels of fault codes exist: (1) Non-
critical and (2) Critical. In general a
non-critical fault permits all (or nearly
all) operations to proceed and a critical
fault prevents all (or nearly all) opera-
tions from proceeding. Detailed expla-
nations are given for each fault code
and how to diagnose and troubleshoot
problems by fault code displayed in the
"TROUBLSHOOTING" section of this
manual.
Active faults of either level will be dis-
played at the thermostat in the
"ACTIVE FAULT" area of the thermo-
stat. To enter the furnace "ACTIVE
FAULT" area using a communicating
thermostat, see the installation and
operation instructions for that thermo-
stat.
1
2
FURNACE USER MENUS
NOTICE: ALL TEMPERATURE
VALUES DISPLAYED IN USER
MENUS ARE DISPLAYED IN
DEGREES FAHRENHEIT AT ALL
TIMES. THIS IS TRUE EVEN IF
THE THERMOSTAT IS SELECTED
TO CELCIUS (C.). USER MENUS
CAN NOT DISPLAY TEMPERA-
TURES IN CELCIUS.
Systems configured for communica-
tions will have some advantages
over traditional control (24VAC ther-
mostats) systems. One advantage is
that a variety of information that can
be useful for configuring the furnace/
system and diagnostic/troubleshoot -
ing information can be displayed at
the thermostat.
The bulk of this information can be
found inside the user menus. The
procedure for entering (and exiting)
the user menus will vary depending
on the thermostat or service tool that
is used. To enter, navigate or exit
the furnace "USER MENU"s using a
communicating thermostat, see the
installation and operation instruc-
tions for that thermostat.
Navigating the user menus is
straight-forward. The menu follows
the logic tree shown in Figure 40 (a
& b).
NOTE: There may be a delay of
several seconds when accessing he
user menus or sub-menus. This is
normal.
51