Digitronic CamCon DC50 Manual

Digitronic CamCon DC50 Manual

Digital cam switch unit
Table of Contents

Advertisement

Digital Cam Switch Unit
CamCon DC50/51
Digitronic Automationsanlagen GmbH
Steinbeisstraße 3 • D - 72636 Frickenhausen • Tel. (+49)7022/40590-0 • Fax -10
Auf der Langwies 1 • D - 65510 Hünstetten-Wallbach • Tel.(+49)6126/9453-0 • Fax -42
Internet: http://www.digitronic.com • E-Mail: mail@digitronic.com
2 rue René Laennec 51500 Taissy France
E-mail:hvssystem@hvssystem.com
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
Site web : www.hvssystem.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CamCon DC50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Digitronic CamCon DC50

  • Page 1 Steinbeisstraße 3 • D - 72636 Frickenhausen • Tel. (+49)7022/40590-0 • Fax -10 Auf der Langwies 1 • D - 65510 Hünstetten-Wallbach • Tel.(+49)6126/9453-0 • Fax -42 Internet: http://www.digitronic.com • E-Mail: mail@digitronic.com 2 rue René Laennec 51500 Taissy France E-mail:hvssystem@hvssystem.com Fax: 03 26 85 19 08, Tel : 03 26 82 49 29 Site web : www.hvssystem.com...
  • Page 2 The CamCon DC50/51 and this instruction manual are protected by copyright. All rights are reserved. Neither the CamCon DC50/51, nor this document may be copied as a whole or partially, photocopied, reproduced, translated or transferred to electronic media of any kind or into machine readable format without prior written permission by the company Digitronic Automationsanlagen GmbH.
  • Page 3: Table Of Contents

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 TABLE OF CONTENTS 1. Introduction ............................8 2. Operating Pinciples..........................9 2.1. Speed Compensation ........................10 2.1.1. Measuring delay time for Speed Compensation................12 2.1.1.1. Measuring delay time through actual differences ..............12 2.1.1.2.
  • Page 4 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.2.1. Changing the display........................31 7.2.2. Program change .......................... 32 7.2.3. Program name ..........................32 7.3. Cam programming .......................... 33 7.3.1. Output selection for programming ....................33 7.3.2. Program selection for programming .................... 34 7.3.3.
  • Page 5 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.4. Cable length / Cycle time ......................60 7.4.4.1. The cable length ........................60 7.4.4.2. The cycle time of the CamCon....................60 7.4.5. The special outputs........................60 7.4.5.1. The security output........................60 7.4.5.2.
  • Page 6 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 9.5. Problem: "Pos - Err:5"........................81 9.6. Problem: An "Pos-Error:" occurs during operation................81 9.7. Problem: "RAM-Full" = RAM memoryis full..................81 9.8. Problem: The EEProm memory is full..................... 82 9.9. Problem: Outputs will not activate....................82 9.10.
  • Page 7: Introduction

    The following characteristics testify the excellence of the CamCon: Tested and reliable hardware Short-circuit-proof outputs Graphic liquid crystal display with 128x64 pixels in the CamCon DC50,51. Large and clearly visible 7-Segment display for program, position and speed on CamCon DC30,33 and 40.
  • Page 8: Operating Pinciples

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 2. Operating Pinciples Diagram: Principles of a Cam Switch Unit A principle for better comprehension of the function of a Cam Switch Unit is here presented. It has 3 outputs with the following cams:...
  • Page 9: Speed Compensation

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 2.1. Speed Compensation Each mechanical switch component (e.g. shield, magnetic valve) has a delay time, i.e. the time between the start signal and the actual switching of the contacts. In processes where positioning is executed on a moving system, this can cause problems.
  • Page 10 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 A small example in figures was designed to eludicate: Supposing the drive cylinder with the measuring system has a circumference of 360mm, so that one millimeter of the circumference corresponds to exactly one angle degree of the measuring system.
  • Page 11: Measuring Delay Time For Speed Compensation

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 2.1.1. Measuring delay time for Speed Compensation Several ways of measuring delay time of a relay or valve are available. 2.1.1.1. Measuring delay time through actual differences First the switch-ON point of a valve or relay is programmed. We assume that the programmed switch point lies at 200 degrees in this case.
  • Page 12: Speed Compensation Using Off-Centre Pressure, E.g. Brake Functions

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 2.1.2. Speed Compensation using off-centre pressure, e.g. brake functions The Speed Compensation of the CamCon Cam switch unit works using a linear function. If, for example, the speed doubles, then the shift of the compensated cam changes and also moves forward by twice the amount.
  • Page 13: Separate Delay Time For Speed Compensation Of Switch-On And Switch-Off Points

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 2.1.3. Separate delay time for Speed Compensation of switch-ON and switch-OFF points For CamCon devices of Software from 3/2002 Speed Compensation is now available for separate switch-ON and switch-OFF points. This is necessary since some valves need longer to switch OFF than to switch ON.
  • Page 14: Installation

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 3. Installation The unit is inserted into a cutout for front plate installation (see chapter "3.1. Dimensions" on page 14). Connect the groundig pins on the back of the encasement as well as the cable cover to a grounding point of the switchboard door in the shortest possible way.
  • Page 15: Electrical Connections

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4. Electrical connections 4.1. Pin allocation of the CamCon CamCon Fig.: Backview of the CamCon with pin allocation 4.1.1. Pin allocation of the analog output 0V signal mass for the analog output...
  • Page 16: Pin Allocation Of The Incremental Measuring System

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.1.3. Pin allocation of the incremental measuring system 0V voltage supply for theincremental measuring system (encoder) A Imp. (+) A Imp. (-) B Imp. (+) B Imp. (-) +24V DC voltage supply for the incremental measuring system (encoder) C1 Imp.
  • Page 17: Pin Allocation Of The Voltage Supply

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 0V voltage supply for the outputs 17 to 32 Output 17 Output 18 Output 19 Output 20 Output 21 Output 22 Output 23 Output 24 +24V DC voltage supply for the outputs 17 to 32...
  • Page 18: Pin Allocation Of The Serial Rs485 Interface

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.1.7.2. Pin allocation of the serial RS485 interface DSUB 9 pinboard: RS485 Interface for PC attachment or for the networking of many devices (max. 1000m cable length). Closedown resistors for RS485...
  • Page 19: Pin Allocation Of The External Interface

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.1.8. Pin allocation of the external interface If you ordered the external interface along with the CamCon, you have the possibility to extend your CamCon by a CamCon DC91/IO, DC92/I or DC16/IO. The extensions are clipped on to a rail in the clipboard.
  • Page 20: The Measuring System

    Warning: Reading a binary encoded value into the CamCon is only permitted after consultation with the Service department of the company Digitronic. ,Version from: Aug. 04 Page: 20 2 rue René Laennec 51500 Taissy France E-mail:hvssystem@hvssystem.com...
  • Page 21: Incremental Measuring System Input

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.2.3. Incremental measuring system input Systems with 90° phase shift signals such as turning angle encoders, glass measuring rods or flow measuring devices. At the present time incremental measuring inputs for the CamCon DC16/50/51/115/300 and DC1756 are available as an option.
  • Page 22: Incremental Hiperface Measuring System Input With Sincos Level

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.2.3.3. Incremental Hiperface measuring system input with SINCOS level The Hiperface measuring system is a feedback system for servo-motors of the company Stegmann. It is a mixed system and consists of an absolute measuring system and an incremental measuring system.
  • Page 23: Pll Measuring System Input

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.2.5. PLL measuring system input Systems with Phase - Lock - Loop data recording. In these systems the actual value is found through interpolation of initiator impulses. This measuring system is applied to machines with constant speed and with a cyclic pulse.
  • Page 24: The Outputs

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 4.3. The outputs The CamCon has, concerning each upgrading level, up to 32 outputs and with extreme extension (e.g. CamCon DC16/IO, DAC16 or DC91/IO) up to 200 short circuit-proof outputs. They deliver 24Volt high active signals and are not potentially free towards the CPU.
  • Page 25: Outline Of The Operator Terminal

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 5. Outline of the operator terminal 5.1. Frontview CamCon 5.2. The liquid crystal display (LCD) The display unit of the CamCon 50 contains a graphical LCD with 128x64 picture elements. For the visual user prompting, all menus concerning the programming of the unit, state and error messages of the outputs, as well as the current position and speed, are represented here.
  • Page 26: Outline Of Key Functions

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 5.5. Outline of key functions cursor down cursor up cursor to the left, shifting cams cursor to the right, shifting cams choose cam activation point, character selection during text input, (or PC 'PageUp' key)
  • Page 27: Text Input

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 5.8. Text input With menu points, in which texts have to be implemented, the keys function together with keys like a coordinate control. You select the desired position for the first character, using the keys.
  • Page 28: Commissioning

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 6. Commissioning Before switching the device on for the first time, please check its wiring (see chapter 4.1. Pin allocation on page 15). Attention: With induced loads the outputs have to be switched with a freewheeling diode.
  • Page 29 Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 After about 5 sec. the display returns to the configuration menu. This waiting time depends on the size of the used EEPROM, since the memory has to be formatted. With the use of a 32k - EEPROM it is increased to approximately 2 min.
  • Page 30: Operation Of The Camcon

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7. Operation of the CamCon 7.1. The main menu The programming always starts at the main menu. No matter in which state of programming you are, you can always reach the main menu by pressing the (several times, if necessary).
  • Page 31: Program Change

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.2.2. Program change With the CamCon you are capable of storing several programs. To choose one of these programs you have to be in the standard display. The selection of a desired program is done as follows: Press the key, the display shows the request for your user code.
  • Page 32: Cam Programming

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3. Cam programming To get to the actual cam programming select "Cam programming" in the main menu. The display switches to the programming menu: The upper part shows the current actual position, the switched state of the selected output and the chosen program.
  • Page 33: Program Selection For Programming

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.2. Program selection for programming You reach the input of the output number by pressing the key. You skip this by pressing the and enter the program selection for the programming.
  • Page 34: Programing Time-Cams

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.4. Programing Time-Cams By pressing you get to enter the starting number, which can be adopted by confirming with key . After that, you are put forward to entering the delay time.
  • Page 35: Programming The Output Name

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.5. Programming the output name You reach the input of the output number by pressing the key. You skip this by pressing the and enter the input of the output name of this output.
  • Page 36: Adding Cams

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.7. Adding cams In case you want to program additional cams on this output, you have to use the key. When you press this key the following is displayed on the display: Here you can enter the positions for the activation and the deactivation point for the cam, as is described in the chapter "7.3.6.
  • Page 37: Cam Deletion

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.10. Cam deletion If you want to completely erase a cam, select the cam using the keys and press the key, causing the following question to be displayed: To delete the cam, move the cursor to "yes" with the...
  • Page 38: Copying Programmed Outputs (Cam Tracks)

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.12. Copying programmed outputs (cam tracks) With the CamCon you have the option to copy all the cams you have programmed on one output to additional outputs. First press the key to enter the input of the output number. Select the output that you want to copy to the previous selected output with the numeric keys.
  • Page 39: Deleting Programs

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.14. Deleting programs If you want to erase a whole program, you have to press the key to enter the input of the output number. Skip it by pressing the key, and you enter the program selection for programming.
  • Page 40: Examples For Cam Programming

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.16. Examples for cam programming 7.3.16.1. First cam programming Task: After a complete deletion of the program memory and a successful initialization of the system, a cam shall be programmed for output 4 from 100° to 200° with a speed compensation of 100ms Solution: Choose the main menu point "Programming".
  • Page 41: Programming Additional Cams On An Output

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.16.2. Programming additional cams on an output Task: Program an additional cam from 300° to 330° in program 0, on output 4 with the cam from 100° to 200°. Solution Select the menu point "programming" in the main menu.
  • Page 42: Deletion Of A Particular Cam

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.16.3. Deletion of a particular cam Task: In program 0 the inserted cam between 300° and 330° shall be erased. Solution: Select the menu point "cam programming" in the main menu.
  • Page 43: Programming Analog Cams

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.17. Programming analog cams If your CamCon is equipped with analog outputs, and you have activated the option of analog cams (see chapter "7.4.5.7. Configuration of the analog cams" on page 61), the last "normal" output will be displayed as the first analog output after pressing the .
  • Page 44: Creating The First Analog Cam

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.3.17.1. Creating the first analog cam To program your first analog cam, choose the program and the desired output for programming (see chapters: "7.3.2. Program selection for programming" and "7.3.1. Output selection for programming").
  • Page 45: Unit Configuration (System Setting)

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4. Unit configuration (system setting) Before you are able to use this device, you have to give it all the information about the parameters of your measuring system. Select the menu point "System setting"...
  • Page 46: Controlling The Measuring System

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.3. Controlling the measuring system The option "Vmax" of the menu enables entering the tolerated steps per cycle of the actual value.. This enables controlling a measure-system. The required value is calculated of the CamCon's actual cycle-time, the measuring system's physical resolution und the device's Speed.
  • Page 47: The Electronic Gear

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.4. The electronic gear In the menu point "Measuring system" a factor for a measuring range transformation can be entered. Through this the physical measuring range e.g. of a rotation encoder is transformed into a new, for the user effective visible measuring range.
  • Page 48: Configuration Of A Special Measuring System

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.6. Configuration of a special measuring system You have the possibility with CamCon to configure a special measuring system, according to the following steps: To configure the special measuring system press key.
  • Page 49: Parallel - Gray Measuring System

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.6.2. Parallel - Gray measuring system If you selected "PARAL." for your special measuring system in the measuring system input, the following menu is created: Enter the resolution of the parallel gray measuring system.
  • Page 50: Multiturn Measuring System With Electronic Gear

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 "C1 or áC2" Counter is set to 0, If input C1 is high or a signal at input C2 changes from low to high. "C1 or âC2". Counter is set to 0, If input C1 is high or a signal at input C2 changes from high to low.
  • Page 51: Pll Measuring System

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.6.5. PLL measuring system If you selected "PLL" for your special measuring system in the measuring system input, the following menu is created: The PLL measuring system determines the way out of temporal interpolation of a measuring impulse.
  • Page 52: Rs232 Measuring System

    Press the key to confirm your inputs and exit this menu. Attention: This measuring system may only be used on a CamCon DC50/51, since it blocks the serial interface, making the programming via a PC or a terminal impossible! 7.4.1.6.8.
  • Page 53: Sim - Measuring System Simulator

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.6.9. SIM - measuring system simulator Having selected "SIM" in the measuring system menu, the following menu appears: The SIM - measuring system - simulator enables crearting ways or time actual values without measuring system, i.e.
  • Page 54: Deleting The Special Measuring System

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.1.7. Deleting the special measuring system The special configuration of the measuring system can be removed as follows: Select the menu point "Measuring system" in the configuration menu. following menu displayed: Select the special measuring system with the keys.
  • Page 55: The Measuring Offset

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.2. The measuring offset If you selected the menupoint "Measuring offset" in the system setting menu, the measuring offset menu appears on the menu: Here you can indicate, using the keys, wether your controlling system is a rotatory (e.g.
  • Page 56: Actual Position Preset

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.2.4. Actual position preset In the measuring offset menu you have the possibility with the rotary system and the linear system to set the actual position to a new value by creating a new input (preset).
  • Page 57: The Speed Adjustment

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.3. The speed adjustment If you selected the menu "Speed" in the system setting menu, the speed adjustment menu appears on the display: You can use it to optimally adjust the speed of the device to the speed of the gear.
  • Page 58: Accuracy Of The Speed Display

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.3.4. Accuracy of the speed display During operations the speed display usually fluctuates by a certain value. These fluctuations are accounted for in the measuring priciple for the speed, since it is a scanning system.
  • Page 59: Cable Length / Cycle Time

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.4. Cable length / Cycle time If you selected the menu "Cable length/Cycle time" in the system setting menu, the following menu is set up on the display: 7.4.4.1. The cable length...
  • Page 60: The Output Of The Actual Position

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.5.2. The output of the actual position The CamCon offers the possibility to put the physical actual position out to outputs. It is used when several CamCon need the same actual position (Master Slave connection).
  • Page 61: The Analog Speed Output

    7.4.5.6. The analog speed output CamCon emitts a voltage (proportional to the speed) on the first analog output (pin 2 at CamCon DC50), 0 to -10V with a negative rotation direction and 0 to +10V with a positive rotation direction, if the menu point "Speed Analog"...
  • Page 62 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 When you confirm the format with the , you enter the input for the minimum value. Note that CamCon always calculates with an accuracy of 16 Bit. The minimum value is the bit value 0 (e.g. -10V or 4mA) and the maximum value is the bit value 65535 (e.g.+10V or 20mA).
  • Page 63: The Analog Position Output

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.5.8. The analog position output The analog position output of the CamCon can be programmed with a software version of at least DC50.20, by the input of an analog cam. Herefore you program an analog cam, that emitts -10V at an actual position of 0 degrees and +10V at an actual position of 359 degrees (see chapter "7.3.17.
  • Page 64: Setting The External Program Selection

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.6.7. Setting the external program selection With the CamCon you have the possibility to externally select the desired program number through the inputs. Here you enter the number of programs that can be selected externally, and this simultaneously predefines how many inputs will be used for this purpose.
  • Page 65: Masterprogram

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.4.7. Masterprogram Having selected "Masterprogram" in the menu "system config" you will get to the following display. Here you are able to define Cams for different products and programms. They could be necessary if your plant produces different types of products that have only very little differences concerning their Cam-adjustement.
  • Page 66: Unit Configuration

    This can be overcome by sending the unit back to Digitronic or with the entry of a special supervisor number. You can aquire this number with a phonecall to Digitronic Automationsanlagen.
  • Page 67: Deletion Of A User Key

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 13. Choose between "yes" and "no" with keys 14. Press the key. The cursor moves to the input field for the access to the outputs, generally and for every output. 15. Choose between "yes" and "no" with keys 16.
  • Page 68: Complete Deletion

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.5.2. Complete deletion If you selected the menu point"Complete deletion" in the "Unit configuration" menu, the display shows : You can move the cursor to "yes" with the key and confirm it with After a short while the display returns to the main menu.
  • Page 69: Unit Configuration

    The standard mode operates with point to point communication, i.e. you can only connect 2 devices, e.g. a CamCon to a PC or a CamCon to a CamCon DC50/51 Terminal. Since this communication mode does not use any protocol security, its usage is only allowed for testing purposes.
  • Page 70: Input Of The Unit Number

    CamCon. 7.5.3.2.1. PLC Logic Module The firm Digitronic Automationsanlagen GmbH is an accomplished and well-known supplier and developper of electronic cam controllers for the industry. The experiences of connecting PLC controlls and cam controllers, collected in years of close cooperation with the users, have been regarded during the creation of the PLC Logic Module.
  • Page 71: Plc Logic Module With Text Display

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 Example 2: Output depending on the rotation direction. Output 1 of the CamCon is Output 1 of the CamCon is enabled when the rotation enabled when the rotation direction output 32 direction output 32 is active.
  • Page 72: Analog Outputs

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.5.3.3. Analog outputs The electronic cam controllers of the CamCon series are equipped with analog outputs (CamCon DC40/50/51 optionally, CamCon DC115 as a standard), via which speed, position or the cam values can be emitted as analog signals.
  • Page 73: Locking Eeprom Memory

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.5.3.4. Locking EEProm memory If an PLC-controll writes or programs parameter, Cams or Delay-Times cyclical (eg. DC300 or CP16) the unit's EEProm-Memory will be destroyed after a short time. If cyclical programming is, for a certain reason, necessary, you therefore have to lock the EEProm.
  • Page 74: Language

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.5.4. Language If you selected the menu point "Language" in the "Configuration" menu, the menu for the language setting appears: Here you can move the dark field to the desired language using the keys .
  • Page 75: User-Menu/Op-Functions

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 7.5.5.2. User-Menu/OP-functions If you choose the menu-point "Configure User" in the menu "User menu", the following menu appears on your display. Here you are able to feed in own input- or displayfunctions into the CamCons Standart-Display. This helps the final customer to change or controll Cams, delay-times and Variables of the PLC-Logic- Module without having to interfere with the units sub-menus.
  • Page 76: Device Info

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 8. Device info If you want to get an overview of whole configuration of the CamCon, you should select the information menu of the unit configuration. Select the main menu point "Unit configuration", and press the key during the input of the user code (the input of the user key is not required here) or you press the key in the "configuration menu".
  • Page 77 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 Factor of the speed display Display format of the speed display 100% value for the speed display Accuracy of the speed display Display menu of the display type / Input for the display change.
  • Page 78: Stack Info

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 Mode of the serial interface Unit number additional options of the e.g. PLC option or PLC option with text display Number of internal analog outputs CPU - Speed (clock) 16 or 25 Mhz Hardware PLC - acceleration (on/off) Configuration of the analog cam 1,2, up to 13.
  • Page 79: Error Messages And Removal Of Errors (Faq)

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 9. Error messages and removal of errors (FAQ) The error messages appear on the standard display or in CamCon DC16, 90, 115, 300 and 1756- DICAM without a display of their own through the status LED or status bits.
  • Page 80: Problem: "Pos - Err:3

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 9.4. Problem: "Pos - Err:3". Possible causes: The resolution of the connected measuring system is not in accord with the input resolution. The measuring system is faulty. The actual value is outside the range which was entered in the menu path setting for linear systems.
  • Page 81: Problem: The Eeprom Memory Is Full

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 9.8. Problem: The EEProm memory is full. Cause: Too little memory space available in the EEPROM for the storage process. Solution: Please contact your customer service representative if you require an EEProm storage extension.
  • Page 82: Problem: "Clear

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 9.13. Problem: "Clear.." Cause: The CamCon is waiting for the arrival of the Clear signal in an incremental measuring system. Solution: Set the Clear signal ON or activate an actual value Preset. The result is the immediate release of the Cam Switch Unit.
  • Page 83: Menu Outline

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 10. Menu outline ,Version from: Aug. 04 Page: 83 2 rue René Laennec 51500 Taissy France E-mail:hvssystem@hvssystem.com Fax: 03 26 85 19 08, Tel : 03 26 82 49 29 Site web : www.hvssystem.com...
  • Page 84: Calculation Eeprom Cam Storage

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 11. Calculation EEPROM cam storage In the CamCon you have the opportunity to extend the EEPROM Cam storage. The storage space required for programming is influenced by the following factors: 1. Basic requirement = 256 Bytes 2.
  • Page 85: Calculation The Ram Storage-Requirement For Camcon

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 12. Calculation the RAM storage-requirement for CamCon The required RAM-main storage (not similar to the constand value - Camstorage or the EEPROM) depends on 7 factors: 1. Standard consumption (approximately 100000 Byte) 2.
  • Page 86: Technical Data Of The Camcon

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 13. Technical data of the CamCon Display ..........graphical display with 128x64 pixels for user prompting and programming (optional with background illumination) Number of outputs .......8, 16, 24, 32 expandable up to 200 through the expansion bus Number of inputs........8, 16 expandable up to 200 through the expansion bus.
  • Page 87: Key Word Table

    Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 14. Key word table 3964(R) ..............................70 Actual position preset..........................57 Actual position, Output........................... 61 Adding cams ............................37 Adding cams, Example .......................... 42 AG615 - Single - Multiturn - Measuring system ..................53 Analog cam, Adding..........................
  • Page 88 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 Dis.value with analog cams ........................63 Display format, Actual position....................... 48 Display, Change............................. 31 Display, LCD ............................26 Display, Standard........................... 31 Display, Type ............................59 DP adresse ............................76 EEPROM cam storage, Calculation....................... 85 EEProm storage is full ...........................
  • Page 89 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 Menu, Selection ............................. 27 millenium ..............................3 Movement direction, Change ......................... 48 Multiturn measuring system with electronic gear................... 51 Multiuser..............................70 No contact to unit XX ..........................80 Offset ..............................56 OP - Function............................
  • Page 90 Digitronic Digital Cam Switch Unit Automationsanlagen GmbH CamCon DC50/51 RS232 as a measuring system ......................24 RS232 measuring system........................53 S5 - L1..............................70 Security output ............................60 Ser.mode ............................... 70 Serial interface ............................18 Serial interface RS232 ........................... 18 Serial interface RS485 ...........................

This manual is also suitable for:

Camcon dc51

Table of Contents