CHAPTER 10: MODBUS PROTOCOL

Administrator Login and Commands via Modbus for 8 Series Relays

869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
SLAVE RESPONSE
DATA STARTING ADDRESS
NUMBER OF SETPOINTS
CRC
Logging in as Administrator
Logging in as Administrator is demonstrated in the example below. The process requires
writing 44 bytes which consist of the Role ID and Password. Password characters are 22
bytes and role characters are also 22 bytes. The logging in must be done using a single
Modbus command using Function 10H (Store Multiple Setpoints).
The following table shows data to be written to the relay to login as Administrator. The
relay password in this example is 0.
Table 10-16: Data Written to Relay to Login as Administrator
Description
Role Characters 1 and 2
Role Characters 3 and 4
Role Characters 5 and 6
Role Characters 7 and 8
Role Characters 9 and 10
Role Characters 11 and 12
Role Characters 13 and 14
Role Characters 15 and 16
Role Characters 17 and 18
Role Characters 19 and 20
Role Characters 21 and 22
Password Characters 1 and 2
Password Characters 3 and 4
Password Characters 5 and 6
Password Characters 7 and 8
Password Characters 9 and 10
Password Characters 11 and 12
Password Characters 13 and 14
Password Characters 15 and 16
Password Characters 17 and 18
Password Characters 19 and 20
Password Characters 21 and 22
Table 10-17: Login as Administrator Function Format
Slave# Function Data
Number
Starting
of
Address
Setpoints
FE
10
F322
0016
BYTES
EXAMPLE
2
04 5C
2
00 02
2
82 7A
Memory Map Address
DEC
HEX
62242
F322
62243
F323
62244
F324
62245
F325
62246
F326
62247
F327
62248
F328
62249
F329
62250
F32A
62251
F32B
62252
F32C
62253
F32D
62254
F32E
62255
F32F
62256
F330
62257
F331
62258
F332
62259
F333
62260
F334
62261
F335
62262
F336
62263
F337
Byte
Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7 Data 8 Data 9
Count
2C
4164 6D69 6E69 7374 7261 746F 7200 0
MODBUS PROTOCOL
DESCRIPTION
setpoint address 04 5C
2 setpoints
CRC error code
Value to be written
DEC
HEX
16740
4164
28009
6D69
28265
6E69
29556
7374
29281
7261
29807
746F
29184
7200
0
0000
0
0000
0
0000
0
0000
12288
3000
0
0000
0
0000
0
0000
0
0000
0
0000
0
0000
0
0000
0
0000
0
0000
0
0000
0
10-7