Unitest 9061 Instruction Manual page 15

Telaris fi/rcd-analyzer
Table of Contents

Advertisement

I∆N:
Display contact voltage
The measurement results may be saved by
pressing key Store (25).
If the condition of a faulty socket is to be saved,
first press key "Start" (22). Upon hearing the
"Error Signal", press key "Store" (25).
If due to the ramp current the contact voltage
is exceeded, the measurement is interrupted
and the current is displayed at the level at which
the excess occurred.
If trip time tRCD of RCD exceeds 300ms, the mea-
surement value for an trip time is displayed as
">300ms". The "Attention" symbol (1) is displayed
and for trip time display, the symbol for overload (2)
appears.
I∆N:
Starting of RCD Test
I∆N:
To make sure that the RCD is tripping correctly, a
standard test (tRCD/VC) has to be carried out. Ex-
ample: A correctly functioning RCD has a trip time
of ">300ms" at 50% I∆N, whereas the trip time
smaller than 300ms. When performing standard
test at I∆N.
If the RCD already trips at 50 % I∆N or not at
all at a residual current value higher than 100
% I∆N, the RCD is faulty or the incorrect nom-
inal residual current has been selected. The at-
tention symbol (1) is displayed and the symbol
for exceeding the limit (2) is indicated togeth-
er with the trip current (tRCD) display
I∆N:
15