SERVICE ACCESS
Access to all serviceable components is provided at the following loca-
tions:
• Coil guards
• Unit top panel
• Corner posts
• Blower access panel
• Control access panel
• Indoor coil access panel
• Compressor access panel
• Heat exchanger access panel
Refer to Figure 4 for location of these access locations and minimum
clearances in Table 4.
CAUTION
!
This system uses R-410A Refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gage sets, hoses, refrigerant containers and recovery systems must
be designed to handle R-410A. If you are unsure, consult the equip-
ment manufacturer. Failure to use R-410A compatible servicing
equipment may result in property damage or injury.
WARNING
!
Wear safety glasses and gloves when handling refrigerants. Failure
to follow this warning can cause serious personal injury.
Refer to Figure 16 for the R-410A Quick Reference Guide.
THERMOSTAT
The room thermostat should be located on an inside wall approximately
60" above the floor where it will not be subject to drafts, sun exposure
or heat from electrical fixtures or appliances. Sealant should be used
behind thermostat to prevent air infiltration. The manufacturer's instruc-
tions are enclosed with the thermostat for general installation proce-
dure. Color coded insulated wires (minimum #18 AWG) should be used
to connect thermostat to unit. See Figure 6. The thermostat must be a
heat pump thermostat able to control fossil fuel backup heat. A 4H/2C
dual fuel heat pump thermostat is to be used.
Do not use power stealing thermostats.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the current N.E.C.
ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be
electrically grounded in accordance with local codes or, in their
absence, with the N.E.C./C.E.C. Voltage tolerances which must be
maintained at the compressor terminals during starting and running
conditions are indicated on the unit Rating Plate and Table 1.
Table 5: Electrical Data
Model
24050
208/230-1-60
24075
208/230-1-60
30050
208/230-1-60
30075
208/230-1-60
36065
208/230-1-60
36100
208/230-1-60
42065, 42100
208/230-1-60
48065, 48100, 48125
208/230-1-60
60065, 60100, 60125
208/230-1-60
NOTES:
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size.
8
Compressor
Voltage
RLA
LRA
11.7
58.3
11.7
58.3
13.1
73.0
13.1
73.0
15.3
83.0
15.3
83.0
17.9
96.0
21.2
104.0
28.8
152.9
The wiring entering the cabinet must be provided with mechanical strain
relief.
A fused disconnect switch should be field provided for the unit. If any of
the wire supplied with the unit must be replaced, replacement wire must
be of the type shown on the wiring diagram.
Electrical service must be sized properly to carry the load. Each unit
must be wired with a separate branch circuit fed directly from the main
distribution panel and properly fused.
Refer to Figure 7 for typical field wiring and to the appropriate unit wir-
ing diagram for control circuit and power wiring information. Unit comes
wired for 230 Volts power. If supply power is 208 Volts, wires connected
to control transformer 230V tap must be moved to the 208V tap.
Minimum wire size of 18 AWG wire should be used for all eld
installed control wiring.
THERMOSTAT
C
R
O
Y or Y1
Y2
G
W2
W1
HUM
NOTE:
Heat Anticipator should be set at 0.35 AMPS for all models.
FIGURE 6: Typical Field Control Wiring Diagram For Dual Fuel
Models
CONTACTOR
REFER TO ELECTRICAL
GND
DATA TABLES TO SIZE
LUG
THE DISCONNECT
FIGURE 7: Typical Field Power Wiring Diagram
OD Fan
Supply
Motor
Blower Motor
MCC
FLA
FLA
18.2
0.7
2.6
18.2
0.7
3.8
20.4
0.8
2.6
20.4
0.8
3.8
23.8
1.7
3.8
23.8
1.7
5.4
28.0
1.7
5.4
33.0
1.7
5.4
45.0
1.7
7.0
CONTROL HARNESS
BLUE
C
RED
R
ORANGE
O
YELLOW
Y1
YELLOW/BLACK
Y2
GREEN
G
WHITE/BLACK
W2
WHITE
W1
GRAY
HUM
FIELD SUPPLIED
DISCONNECT
SINGLE
PHASE
POWER
SUPPLY
Max Fuse
1
MCA
3
Breaker
(Amps)
(Amps)
17.9
25
19.1
30
19.8
30
21.0
30
24.6
35
26.2
40
29.5
45
33.6
50
44.7
70