York PHG6A24 Installation Manual page 25

Phg6 series single package heat pump / gas heat
Hide thumbs Also See for PHG6A24:
Table of Contents

Advertisement

5. Once the correct BTU (kW) input has been established, turn the
gas valve to OFF, and turn the electrical supply switch to OFF. Then
remove the flexible tubing from the gas valve pressure port, and
tighten the pressure port plug using the 3/32" (2.4 mm) hex head
wrench.
6. Turn the electrical and gas supplies back on. With the burners in
operation, check for gas leakage around the gas valve pressure
port. Use an approved non-corrosive gas leak detection fluid or
other non-flammable leak detection methods to accomplish the leak
check.
MANIFOLD PRESSURE "U" TUBE CONNECTION
FIGURE 12: Reading Gas Pressure
Adjust as follows:
1. Remove the cap from the valve body. See Figure 11 for location.
2. To decrease the gas pressure, turn the adjusting screw counter-
clockwise.
3. To increase the gas pressure, turn the adjusting screw clockwise.
NOTICE
The correct manifold pressure for natural gas furnaces is 3.5 IWG.
The correct manifold pressure for propane (LP) is 10.0 IWG.
Johnson Controls Unitary Products
Adjustment Of Temperature Rise
DANGER
!
The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 7 "RATINGS & PHYSICAL / ELECTRICAL
DATA".
The supply air temperature cannot exceed the "Maximum Supply
Air Temperature" specified in these instructions and on the furnace
rating plate. Under NO circumstances can the furnace be allowed to
operate above the Maximum Supply Air Temperature. Operating the
furnace above the Maximum Supply Air Temperature will cause pre-
mature heat exchanger failure, high levels of Carbon Monoxide, a fire
hazard, personal injury, property damage, and/or death.
After about 20 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts
about six feet from the furnace where they will not be affected by radi-
ant heat.
The temperature rise (or temperature difference between the return air
and the heated air from the furnace) must lie within the range shown on
the rating plate and the data in Table 6.
After the temperature rise has been determined, the CFM can be calcu-
lated as follows:
Degrees F Temp Rise =
BTUH Output
CFM =
1.08 x Degrees F Temp Rise
Direct Drive Blower
All units have direct drive, enhanced ECM blower motors.
5322625-UIM-A-0417
BTUH Output
1.08 x CFM
OR
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Phg6a30Phg6b60Phg6b36Phg6b42Phg6b48

Table of Contents