Daikin F-Series Service Manual page 110

Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

SiBE12-713
Checking the
Those data can be checked by looking at the service monitor LED indicators, when the wiring
error checking is over, during forced operation, at the stop of the system.
current setting
The LED indicators stop flashing when the forced operation is over.
data on the
LED1...Room A wiring, LED2...Room B wiring
microcomputer
1st flashing LED...Port A piping, 2nd flashing LED...Port B piping
memory
The first stay-on LED means the room that is connected with Port A. The next stay-on LED
means the one connected with Port B.
Example
Let's suppose the LED indicators are flashing as follows.
The above means that Port A is connected with Port B and Port B with Room A (or self-
corrected this way.)
Function and Control
L
A 1 2 3 4
E
D
Green Red
L
A 1 2 3 4
E
D
Green Red
A
Wiring
B
A
Piping
B
Control Specification
L
A 1 2 3 4
E
D
Green Red
Wiring
Piping
99