Daikin FDQ16PY1 Installation Manual page 17

Duct connection type
Hide thumbs Also See for FDQ16PY1:
Table of Contents

Advertisement

WARNING
If the fuses burn up, please call the service agency to replace them.
Please don't replace them by yourself, or else it may result in accident, such as electric shocks.
<<Precautions When Doing Wiring Work>>
NOTE)
• Use round pressure terminals provided with insulation sleeves for
connections to the power terminal block.
• For wiring, use the designated power wire and connect firmly, then
secure to prevent outside pressure being exerted on the terminal board.
• Use an appropriate screwdriver for tightening the terminal screws. A
screwdriver with a small head will strip the head and make proper
tightening impossible.
• Over-tightening may damage terminal screws.
• See the table below for tightening torque for the terminal screws.
Attach insulation sleeve
Power wire
Round pressure terminal
<<Precautions when connecting the ground terminal>>
• When connecting the ground wire, place the round terminal through the
cut-out section of the cup washer. (Otherwise it may result in bad contact
or poor results.)
Cup washer
Cut-out section
English
Tightening torque (N·m)
Remote controller and
branch wiring terminal block
Power wiring terminal block
Ground terminal
Round pressure terminal
Ground terminal
0.79~0.97
WIRING METHOD
(Power wiring,
2.39~2.92
Ground terminal)
3.20~3.91
Tie down tightly with
wire clamp
(accessory (5))
WIRING METHOD
(Branch wire,
Remote controller wiring)
Fig.16
15