Timer Features

Error/
Information
Icon
Service
Icon
Features of the SXT:
Power backup that continues to keep time and the passage of days for a minimum of 48 hours in the event of
power failure. During a power outage, the control goes into a power-saving mode. It does not monitor water
usage during a power failure, but it does store the volume remaining at the time of power failure.
Settings for both valve (basic system) and control type (method used to trigger a regeneration).
Day-of-the-Week controls.
While in service, the display alternates between time of day, volume remaining or days to regeneration, and
tank in service (twin tank systems only).
The Flow Indicator flashes when outlet flow is detected.
The Service Icon flashes if a regeneration cycle has been queued.
A regeneration can be triggered immediately by pressing the Extra Cycle button for five seconds. During
regeneration, the user can force the control to advance to the next cycle step immediately by pressing the
Extra Cycle button.
The Parameter display shows the
display counts down the time remaining for that cycle step. While the valve is transferring to a new cycle step,
the display will flash.
The Parameter display will identify the
"----". Once the valve reaches the cycle step, the display will stop flashing and the Data display will change to
the time remaining.
Setting the Time of Day
1.
Press and hold either the Up or Down buttons until the programming icon replaces the service icon and the
parameter display reads TD.
2.
Adjust the displayed time with the Up and Down buttons.
3.
When the desired time is set, press the Extra Cycle button to resume normal operation. The unit will also
return to normal operation after 5 seconds if no buttons are pressed.
Page 6
Parameter
Display
Display
Programming
Icon
Extra Cycle
Up
Button
Button
current Cycle Step (BW, BF, RR, etc) during regeneration, and the Data
destination cycle step (BW, BF, RR, etc) and the Data display will read
Data
PM
Indicator
Flow Indicator
x1000 Indicator
Down
Button

Advertisement