Grounding The System; Control Circuit Interconnections; Fault Detection System; System Control Panel - Briggs & Stratton 1768-0 Installation Manual

Home generator system
Hide thumbs Also See for 1768-0:
Table of Contents

Advertisement

Available languages

Available languages

Briggs &
Stratton Power Products Home Generator
System
Installation
Manual
Grounding
the System
Installer-supplied minimum 10AWG stranded copper wire
is connected to the generator housing GND lug and routed
through conduit to the Automatic Transfer Switch's GND
bus. Continue the 10AWG wire through conduit to the
main distribution panel ground bus.Torque all wire
connections/fasteners to values recommended in Figure 15.
Generator
grounding rod is used ONLY if required
by local code.
_-_llk']
"- •
..-.,-.
• .L_&vBIM_
CONNECTIONS:
In Main Distribution Panel:
Refer to panel manufacturerspecs
In Transfer Switch:
UTILITY CONNECTION
lugs
GENERATOR CONNECTION
lugs
GND Bar and NEUTRAL Bar:
14-10 AWG
8 AWG
6-4 AWG
Circuit Breakers:
Refer to circuit breaker
manufacturer specs
Control
Circuit
Interconnections
Control
circuit interconnections consist of "Utility"
and
"Load" leads, plus leads "15","205",
and "206".These seven
signal leads must be routed in conduit that is separate from
the AC power leads. Control
lead functions are briefly
described as follows:
• "Utility
I" and "Utility
2" deliver utility power to the
generator's
circuit board.
• "Load I" and "Load 2" are used to operate the exercise
timer on the generator's
circuit board.
• Leads "15","205",
and "206" supply control
signals to the
Automatic
Transfer Switch.
Using installer-supplied minimum
14 AWG stranded copper
wire, connect each control circuit terminal
in the generator
to its corresponding
terminal
in the Automatic
Transfer
Switch.Torque
all wire connections/fasteners
to values
recommended
in Figure 15.
Torque Value
Minimum
Maximum
35 in-rb
45 in-lb
35 in-lb
45 in-lb
20 in-lb
25 in-lb
35 in-lb
Fault
Detection
System
The right on the control panel is referred to as the
Diagnostic LED. It wilt turn on and off in a series of blinks if
certain problems are detected in the HGS.An extra LED
and mounting plate is supplied so that it can be installed at a
convenient insidelocation.The owner will use it to observe
the status of the HGS.
To install the remote LED panel:
• Apply the supplied decal.
• Pullthe LED through the mountingplate from the back
until it snaps in place.
• Using minimum 18AWG wire, connect the remote LED
to the generator control panel using supplied pin
connectors. Use wire nuts to attach wire to LED leads.
• Attach mounting plate to installer-supplied low voltage
electrical box.
Refer to the section "Fault Detection System" in the
Owner's Manual for operation.
System
Control
Panel
Figure 16 depicts the Home Generator
System control
panel, located inside the generator
housing. Brief
descriptions of the controls
used during installation follow.
More information
may be found in the Owner's
Manual
Circuit
Breaker
Hour Met_
15 Amp
Fuse
;et Exercise
Switch
Diagnostic
LED
MANUAL
Switch
AUTO/OFF/MANUAL
Switch
The most important
control
on the generator
is the
"AUTO/OFF/MANUAL"
switch.This
three-position
switch will be referred to herein as
"AUTO/OFF/MANUAL",
and is used as follows:
• "AUTO"
position
is the normal operating position. If a
utility power outage is sensed, the system will start the
generator, let it reach operating
temperature,
then