Tempered Supply, Heat Only

• To terminals R and W1

Tempered Supply, Cool Only

• To terminals R and Y1

Tempered Supply, Heat and Cool

• To terminals R (common), W1 (heat), and Y1 (cool)
CONNECTIONS TO
R
TEMPERED MUA FAN
R
Switch Mounting - Ship Loose for Remote Mounting
S3-1
HEAT
OFF
COOL
Shipped Loose
Make-Up Air Tempering Switch Example
CONNECTIONS TO
R
TEMPERED MUA FAN
R
Switch Mounting - On Control Package
S3-1
HEAT
BL
OFF
COOL
Mounted on Control Package
Make-Up Air Tempering Switch Example
Connections from these terminals will have to be made
to the respective supply fan terminals R, W1 (if used),
and Y1 (if used). Use proper gauge wire for field wiring
depending on the voltage used.
When connecting to Greenheck's tempered Make-Up
Air unit, connect R, W1 (if used), and Y1 (if used) up to
the supply unit and land on R, W1 (if used), and Y1 (if
used). This will be 24 VAC power, so 18 AWG shielded
wire should be utilized.

Combination Fan/Light Switch

• To terminals S1H and S1
S1
S1H
S1
NOTE
For combination light/fans option, light circuit must
not exceed 900W maximum.
®
Make-Up Air (MUA) Interface (Optional)
When the KFCC is interfaced with another Greenheck
supply air unit, this option may omit the redundant
starter in the KFCC, as the supply air unit may already
be provided with one. This will be 24 VAC voltage; so 18
AWG, shielded control wire can be utilized.
Make-Up Air Unit
• From terminal R in MUA control center to terminal R
in KFCC
W1
Y1
• From terminal G in MUA control center to
terminal G in KFCC
R
R
W1
Y1
Power for Shunt Trip (Optional)
If the KFCC is configured with the power for shunt
trip option, the KFCC will have terminals to connect
an externally provided shunt trip breaker coil to
W1
Y1
allow the breakers to be tripped in the event of a fire.
Connections include:
(Externally Provided) Shunt Trip Breakers
• To terminals STH and STN
BL
W1
STH
BL
Y1
Audible Alarm (Optional)
With this option, an alarm will be provided and mounted
on the panel that will sound in the event of a kitchen
fire. This option will be factory-mounted and wired if
selected.
CONNECTIONS TO
TEMPERED MUA FAN
TYP. THRU ALL
EXHAUST STARTERS
13 14
BL
13 14
STB1
STN
STB2
Kitchen Fan Control Center
G
G
R12
BL
11 14
9