Digital Temperature Interlock Configuration - Greenheck KFCC Installation, Operation And Maintenance Manual

Kitchen fan control center
Table of Contents

Advertisement

Digital Style Temperature Interlock Configuration
NOTE
This section only applicable if the KFCC is configured
with digital temperature interlock option.
Pre-programmed, digital temperature controller(s) will be
provided to monitor temperatures detected by sensor(s)
and engage fan(s).
The fan(s) will start running when a temperature
exceeds the set point (defaulted at 90°F) plus differential
(defaulted at 25°F). Once the temperature drops back
below the set point AND the fan(s) have been running
for a minimum run time (defaulted at 5 minutes), the
fan(s) will shut off.
OUTPUT
DIRECT OUTPUT 1
ON
OFF
DIFFERENTIAL
(DEFAULT = 25°F)
SET POINT
(DEFAULT = 90°F)
®
Calibration
Each controller is capable of monitoring up to three
individual sensors. There will be an individual set point
for each sensor input. The temperature set point may
need to be adjusted slightly depending on both ambient
and cooking conditions. To adjust the set points on the
controller, follow these instructions:
1. Press
2. Press
you wish to adjust (St1, St2, or St3).
3. Press
or
value.
4. Press
menu or wait 1 minute.
Show Sensor Values
Press
value, and press these two buttons together again to
see additional sensors connected. "Sd1" represents
sensor input one, "Sd2"represents sensor input two,
and "Sd3" represents sensor input three (respective to
each controller). After 1 minute of no button presses, the
TEMPERATURE
controller will go back to displaying the first
programmed input (see parameters P31, P32, P33).
button. 'St1" will appear.
Set
or
button to navigate to set point that
button to view current set point. Press
Set
button to adjust and press
+
buttons together to exit set point
Set
+
buttons together to show sensor and
Set
Kitchen Fan Control Center
button to store
Set
13