Lights Out In Fire; Additional Fire Contacts; Additional Exhaust Contacts - Greenheck KFCC Installation, Operation And Maintenance Manual

Kitchen fan control center
Table of Contents

Advertisement

Lights Out In Fire (Optional)
This option will turn off the kitchen hood lights in
the event of a fire without the use of a shunt trip
breaker. If provided, this option will be factory wired.
Normal light circuit wiring should be followed. Please
see either Switches (Optional), Lights on page 8
or Combination Light/Fan Switch on page 9 for
additional wiring information.
NOTE
For lights out in fire option, light circuit must not
exceed 900W maximum.
Additional Fire Contacts (Optional)
The KFCC can include additional fire relays for shunt
trips, alarms, or additional utilities that need control
signals to be sent in the event of a kitchen fire. The
additional relay's state will only be changed if the
dedicated fire system is wired into the KFCC. Wiring
from additional relays to terminals will be done at the
factory.
Additional Fire Relay
• Power to terminal C9
• From terminal NO9 (normally open; closes in fire) to
device
• From terminal NC9 (normally closed; opens in fire)
to device
• Power to terminal C10
• From terminal NO10 (normally open; closes in fire)
to device
• From terminal NC10 (normally closed; opens in fire)
to device
RD
C9
BK
A
NO9
12
BR
B
NC9
14
RD
C10
BK
A
NO10
22 21
BR
B
NC10
24
NOTE
Relay contacts will be dry. Power will need to be
provided to the common terminal on each set.
Do not use additional relay contacts for power
interruption to appliances. Contacts are rated up to
250 VAC and 8 amps maximum.
Relay contacts will also switch state in the event
power is lost to the control panel (terminals H1 and
N1).
10
Kitchen Fan Control Center
R5
11
R5
Additional Exhaust Contacts (Optional)
The KFCC can include additional relays for devices that
activate when the exhaust fan is running. Wiring from
additional relays to terminals will be done at the factory.
Additional Exhaust Relay
• Power to terminal C7
• From terminal NO7 (normally open; closes with
exhaust) to device
• From terminal NC7 (normally closed; opens with
exhaust) to device
• Power to terminal C8
• From terminal NO8 (normally open; closes with
exhaust) to device
• From terminal NC8 (normally closed; opens with
exhaust) to device
RD
C7
BK
A
NO7
14
BR
B
NC7
12
RD
C8
BK
A
NO8
24
BR
B
NC8
22
NOTE
Relay contacts will be dry. Power will need to be
provided to the common terminal on each set.
Contacts are rated up to 250 VAC and 8 amps
maximum.
R4
11
R4
21
®