Temperature Sensor(s) - Hood Mounting,
3. Place the J-box plate inside of the octagon extension
ring and place over the hole.
4. Disassemble the compression seal and place through
hole and J-box plate as shown. Tighten the nut inside
the octagon extension ring.
Compression Seal
PN 463570
Gasket
Exploded View (Components)
5. Place the temperature sensor through the
compression seal and tighten the compression fitting
to 35 ft.-lbs. (47.5 Nm).
Additional Octagon Extension
(Optional)
PN 830125
Octagon Cover
PN 380926
6. Wire the sensor. Refer to Electrical Connections
section for instructions on wiring the temperature
sensor.
7. Place octagon cover onto J-box and fasten it.
4
Kitchen Fan Control Center
continued
Octagon Extension
PN 830125
J-Box Plate
PN 732396
Lock Washer
Nut
Temperature Sensor
PN 384925
Temperature Sensor(s) - Duct Collar Mounting
1. Locate the exhaust duct on top of the hood. Find a
spot to mount the sensor where it will not interfere
with fire suppression nozzles or other items installed
in the ducts. If an exhaust fire damper is present in
the hood exhaust collar, it must be removed prior
to temperature sensor installation. A 3/4 to 7/8-inch
(19.0 to 22.2 mm) diameter hole must be cut into the
duct 2 inches (50.8 mm) above the hood top.
0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole
Hood Exhaust Collar
Front Side
2. Place the J-box plate inside of the octagon extension
ring and place over the hole in the exhaust collar.
3. Disassemble the compression seal and place through
hole in duct collar and J-box plate as shown. Tighten
the nut inside the octagon extension ring.
1/4-inch Compression Seal
PN 463570
Quik Seal
Gasket
Exploded View (Components)
4. Place the temperature sensor through the
compression seal and tighten the compression fitting
to 35 ft.-lbs. (47.5 Nm).
Sensor
PN 384925
5. Wire the sensor. Refer to Electrical Connections
section for instructions on wiring the temperature
sensor.
6. Place octagon cover onto J-box and fasten it.
2 inches
(50.8 mm)
Octagon Extension
PN 830125
J-Box Plate
PN 732396
Lock Washer
Nut
Octagon Cover
PN 380926
Additional Octagon
Extension
(Optional)
PN 830125
®

Hide quick links: