Connecting The Refrigerant Piping; About Connecting The Refrigerant Piping; Precautions When Connecting The Refrigerant Piping - Daikin FCAG35AVEB Installer And User Reference Manual

Split system air conditioners
Hide thumbs Also See for FCAG35AVEB:
Table of Contents

Advertisement

1
2~6
a
b
e
4
1
A-A'
a
Drain pipe connection (attached to the unit)
b
Drain hose (accessory)
c
Metal clamp (accessory)
d
Large sealing pad (accessory)
e
Insulation piece (drain pipe) (accessory)
f
Drain piping (field supply)
To check for water leaks
The procedure differs depending on whether electrical wiring is
already finished. When electrical wiring is not finished yet, you need
to temporarily connect the user interface and power supply to the
unit.
When electrical wiring is not finished yet
1 Temporarily connect electrical wiring.
▪ Remove the switch box cover (a).
▪ Connect the user interface (b).
▪ Connect the power supply (1~ 220-240  V 50/60  Hz) and
earth (c).
▪ Reattach the switch box cover (a).
2 Turn ON the power.
3 Start cooling operation (see
page 21).
4 Gradually pour approximately 1  l of water through the air
discharge outlet, and check for leaks.
FCAG35~140AVEB
Split system air conditioners
4P473927-1 – 2017.03
c
d
f
2
5
6
A
A
A'
A'
≤4 mm
d
c
3
b
a
T1
T2
b
Transm.
Forced OFF
a
c
"8.4  To perform a test run"  on
a
Plastic watering can
b
Service drain outlet (with rubber plug). Use this outlet to
drain water from the drain pan.
c
Drain pump location
d
Drain pipe connection
e
Drain pipe
5 Turn OFF the power.
6 Disconnect the electrical wiring.
▪ Remove the switch box cover.
▪ Disconnect the power supply and earth.
▪ Disconnect the user interface.
▪ Reattach the switch box cover.
When electrical wiring is finished already
1 Start cooling operation (see
page 21).
2 Gradually pour approximately 1  l of water through the air
discharge outlet, and check for leaks (see When electrical
wiring is not finished yet).
6.3

Connecting the refrigerant piping

6.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the outdoor unit
▪ Connecting the refrigerant piping to the indoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:
▪ Pipe bending
▪ Flaring pipe ends
▪ Brazing
▪ Using the stop valves
6.3.2
Precautions when connecting the
refrigerant piping
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF BURNING
6 Installation
e
d
c
b
a
"8.4  To perform a test run"  on
Installer and user reference guide
15