04-393 DC INV Tech p 64-110
10-26. Automatic Address Setting
10-26-1. Basic wiring diagram
G
Link wiring
NOTE
G
A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only 1 outdoor unit, leave the ter-
minal plug short-circuit socket on the "Yes" side. At all the other outdoor units, change the socket (from "Yes" to
"No").
G
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
No. 1
Outdoor unit
Terminal plate 1, 2
Terminal plate 1, 2
Indoor unit
Wireless remote
controller
* If wall-mounted type units are used for a simultaneous-operation multi system (group control), refer to 10-16. System Con-
trol (basic wiring diagrams and wiring procedures) on the reverse cover of this manual when wiring.
12/13/04
11:35 AM
Page 93
System address 1
(Change setting to "1")
Inter-unit control
wiring
1-1
1-2
1-3
Remote controller crossover
wiring for group control
System address 2
(Change setting to "2")
Change the terminal
plug (black) short-circuit
socket
No. 2
2-1
2-2
Wired remote
controller
Remote controller crossover
wiring for group control
Fig. 10-25
93
System address 3
(Change setting to "3")
Change the terminal
plug (black) short-circuit
socket
No. 3
Inter-unit control wiring
3-1
3-2
3-3
Wired remote
controller