10-18. Test Run Procedure
Turn ON the indoor
and outdoor power.
Automatic Address
12/13/04
11:35 AM
Page 82
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and
outdoor units.
YES
Is system "single-type"?
Is outdoor unit multiple?
(See 10-22-2) How to Set the Outdoor Unit System Address
Set the outdoor unit system address.
(See 10-22-1) How to Set Automatic Address
Set the automatic address setting from
outside unit or remote controller.
Indicate (mark) the combination number.
Turn ON the indoor and outdoor power.
Set the remote controller to "test run."
Can
operation be
started?
Return the remote controller to normal
control.
(See 10-19)
(See 10-22-1)
NO
NO
YES
(See 10-22-3, 4)
Automatic Address
(See 10-20)
Refer to "Table of Self-Diagnostic
NO
Functions" to check the system.
In addition, refer to Item 10-22 and
correct any items that need to be
YES
corrected.
Note: Check the indoor-side drainage.
(*)
Required for simultaneous-operation
multi systems and for group control.
Fig. 10-18
82